Code E - 87
This code indicates that the unit has
stopped because the generator voltage has not reached
80% of the nominal value 30 seconds after starting. This
could be caused by insufficient motor RPM or a broken
alternator.
batt
This code indicates that the battery
is low. When this code appears, the generator is not
stopped.
WARNING
When a circuit breaker has tripped with a consequent
generator stop, the panel must be reset by pressing the
"OFF" button in order to restart the unit.
INFORMATION
If the unit is started and the alternator does not produce
voltage, or the control panel does not read voltage, the
latter switches off completely after one minute, stopping
the unit.
8 PROTECTION FUSE ( fig. 4 )
1) RELAY CIRCUIT FUSE
2) BATTERY CHARGER FUSE
3) THERMAL SWITCH
9 DIMENSIONS AND WEIGHT ( fig. 7 )
a) Lengh (mm-inch)
b) Width (mm-inch)
c) Height (mm-inch)
Weight (kg-lb)
10 DESCRIPTION WIRING DIAGRAM (fig. 8 )
1
ROTOR
2
STATOR
3
DIODE 3A
4
VARISTOR
5
PRINTED CIRCUIT RELAY
6
POWER TERMINAL BOARD
7
RELAY CIRCUIT TERMINAL BOARD
8
CONTROL PANEL TERMINAL BOARD
9
FUSE 1A
10
CAPACITOR
11
BATTERY CHARGER REGULATOR
12
FUSE
13
STARTER
14
BATTERY
15
FUEL PUMP
16
FUEL SOLENOID
17
OIL PRESSURE SWITCH
18
OVERHEAD ENGINE THERMOSTAT
19
WATER TERMOSTAT
20
ALTERNATOR THERMOSTAT
21
THERMAL SWITCH
IS 3.5 - 4.0
IS 5.0 - 6.0
590-23
675-26.6
406-15.9
468-18.4
515-20.2
565-22.2
96-213
130-289
GB
11 TROUBLE MAINTENANCE
12 TROUBLE SHOOTING
COMPLAINT
PROBABLE REASON
Defective starting buttons
Defective fuel solenoid
Defective battery
Battery
cable section
Defective starting motor
Piping fuel filter choked
12V circuit fuse
Avv./Ev.relay
Too much oil in crankcase
Safety device intervention
Overload
Defective governor linkage
Worm valve guides
Blocked valves
Worm cylinder and position rings
Defective injector
Defective injector pump
Defective feeding pump
IS 3.5 - 4.0- 5.0 - 6.0
-
-