When the LCD shows as displayed at left, press the MENU key for 1s, the icon
Display
1. Always on Mode: when the controller is set to always On mode, no matter the charging or discharging state, the load is always powered
on (except in when in protection state).
2. Streetlamp Function: when the load is set to Dusk to Dawn or Evening mode, the Day/Night threshold voltage and the Day/Night delay time
can be set by the mobile phone APP, or RS485, and the load can be turned on or off by the test function during the day charging process.
- Day/Night threshold voltage: the controller recognizes day and night based on the solar array open circuit voltage. This day/night
threshold voltage can be modified according to local light conditions and the solar array used.
Day/Night threshold setting range: 3.0~20.0V (Lithium, default: 8.0V)
Day/Night threshold setting range: 3.0~10/6.0~20/12~40V (Liquid/Gel/AGM, default: 8/16/32V)
- Day/Night delay time: in the evening, when the solar array open circuit voltage reaches the setting day/night detect voltage, you can adjust
the day/night delay time to make the load turn on a little bit later.
Day/Night delay time setting range: 0~30min (default: 0min)
- Test Function: when the controller is working in Dusk to Dawn or Evening mode, press the MENU key for 3s to turn on the load. Press the
MENU key again or the load turns off automatically after 1 minute.
If the controller is operating in always on mode, the test function does not work.
3. User-defined Mode: if the load mode is selected "USE", then you can switch on and off the load output manually by pressing MENU shortly.
The default switching state of the load in manual mode can be changed by mobile APP or RS485. At the same time, the output to the load can be
turned on or off.
If the controller turns off the load due to low voltage protection, overcurrent protection, short-circuit protection or over
temperature protection, the load will turn on automatically when the controller recovers from protection state.
Pushing the MENU button can still activate the function of the key, even during of the above four kinds of protection states.
ICC-6048150
When the icon
appears in the display interface, it means that the parameters can be set. Press the MENU key for 1s, then icon
press OK to change the parameter, when the setting is finished, you can wait 30 seconds to exit the setting mode automatically, or you can press
the MENU to exit the setting mode.
Low voltage protection
When the LCD shows as displayed below, press the MENU key for 1s, the icon
1. Lithium battery: low voltage protection setting range: 12/24/36/48V: 9.0-60.0V (default: 21.0V).
2. Liquid, Gel and AGM Battery: Low voltage protection setting range: 10.8~11.8V/21.6~23.6/32.4~35.4/43.2~47.2V (default:
11.2/22.4/33.6/44.8V).
40
MANUAL DE USUARIO CONTROLADOR CEDRO PLUS
Load mode
Always on Mode: the load output is always switched on.
Dusk to Dawn Mode: The load output is switched on between sunset and
sunrise.
Evening Mode: The load output will be switched on for 2~9hours after sunset.
Manual Mode: The load output can be switched on and off manually by
pressing MENU shortly.
flashes, you can set the load mode:
flashes, you can set the controller low voltage protection:
flashes,