Humidity Control - Daikin UATYA-BBAY1 Manual De Operación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 143

5.4 humidity control

Humidity control devices are managed according to the value measured by the reference probe. The measured value
is compared with the desired value (setpoint), after which the system calculates the difference between these values
and then enables the most suitable devices based on this difference.
The proportional band identifies the control range of the air conditioner system and it is set up with the same values
for both humidification and de-humidification.
The dead zone identifies the range around the setpoint within which the devices are not enabled (it is used to prevent
oscillations in the setup value).
The diagram below shows the behaviour of humidification and de-humidification devices.
The parameters involved are shown in the table.
Parameter
Min
HU1
HU2
HU4
0.0
HU5
0.0
HU6
HU7
HU9
0.0
HU10
0.0
HU11
0
Translation from original instructions
Packaged Rooftop
26
HU4/HU9
HU5/HU10
Fig. 8 Graphical representation of humidity control devices
Max
UM
Description
HU3
%
Relative humidity setpoint
25.0
%
Relative humidity control differential
10.0
%
Relative humidity control neutral area
HU8
g/kg
Absolute humidity setpoint
10.0
g/kg
Absolute humidity control differential
10.0
g/kg
Absolute humidity control neutral area
1
-
Humidity value control type
%
100
0
HU5/HU10
HU4/HU9
HU1/HU6
SdR %-g/kg
We reserve the right to make changes without any prior notice.
4P645203-1
UATYA

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Uatya-bbc2y1Uatya-bbc3y1Fc2Fc3Fc4

Tabla de contenido