Relative Humidity Control With Proportional Control - Daikin UATYA-BBAY1 Manual De Operación

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 143
The value set in parameter "HU11" identifies the reference humidity value, as follows:
- 0 = relative humidity;
- 1 = absolute humidity.
5.4.1

Relative humidity control with proportional control

If parameter "HU11" is set to "0", humidity control is performed according to the relative humidity value.
Relative humidity is managed according to parameter "HU14", which identifies the probe on which the controller
must guarantee maintenance of the entered setpoint, and on parameter "HU12" that determines the type of humidity
control.
The parameters involved are shown in the table.
The values of the parameters are representative. In specific cases, different values can be set.
Parameter
Value
HU4
5.0
HU5
0.5
A graphical representation is shown below.
We reserve the right to make changes without any prior notice.
UATYA
4P645203-1
UM
Description
%
Relative humidity control differential
%
Relative humidity control neutral area
HU4
HU5
Fig. 9 Relative humidity control
%
100
0
HU5
HU4
HU1
SdR %
Translation from original instructions
Packaged Rooftop
27

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Uatya-bbc2y1Uatya-bbc3y1Fc2Fc3Fc4

Tabla de contenido