Installation and User Manual Himalaya D
2.2. Recommended sauna room ventilation
5
4
6
2
Figure 1 Rekommended sauna room ventilation
1. Sauna room
2. Washroom
7. A ventilation valve can be installed here to be kept closed while the sauna is heated and during bathing.
Inlet vent can be positioned in the A zone. Make sure the incoming fresh air will not interfere with (i.e. cool down) the
sauna heater's thermostat near the ceiling.
The B zone serves as the incoming air zone, if the sauna room isn't fitted with forced ventilation. In this case, the exhaust
valve is installed min 1m higher than the inlet valve.
DO NOT ISTALL INLET VALVE WITHIN ZONE C, IF THE SAUNA HEATER'S CONTROL THERMOSTAT IS LOCATED
IN THE SAME ZONE.
For more detailed instructions for installing the sensor, please refer to Section 2.8 on page 7.
2.3. Heating the sauna
Before turning the sauna heater on, make sure the sauna room is suitable for taking a sauna bath. When heated for the
first time, the sauna heater may emit some odour. If you detect any odour while the sauna heater warms up, disconnect
the sauna heater briefly, and air the room. Then turn the sauna heater back on.
You should turn the sauna heater on roughly an hour before you plan to take a sauna bath, so that the stones have time to
heat up properly and the air warms up evenly in the sauna room.
Do not put any objects on the sauna heater. Do not dry clothes on the sauna heater or anywhere in its vicinity.
5
7
1
1
4
3. Electric sauna heater
4. Exhaust valve
C
C
C
C
1000 mm
B
B
3
3
5. Exhaust flue or channel
6. Door to the sauna room
4
A
A
A
min
500 mm
1