Madas MTC10 Manual De Instrucciones página 24

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

5.3 - EVP CONFIGURATION (using the NC auxiliary automatic solenoid valve)
The MTC10 controls valves V1 and V4.
The Burner Control controls valve V2.
The following checks are performed before starting the burner:
1. Leak test V1
2. Leak test V2 and V4
During the test, valve V4 discharges the gas to the outside in a safe place. After the test, the device waits for the signal
provided by the Burner Control. Once the signal is received, V1 on the valve control connector is opened (V4 is kept closed).
The Burner Control opens V2.
Valve Control
MTC10
V1: NC safety solenoid valve
V2: NC work solenoid valve
V4: NC auxiliary valve
P:
T:
LP: Minimum pressure switch
Electrical connections
P
: Low pressure switch
1
P
: High pressure switch
2
24
Madas Technical Manual - 9|9.4 - REV. 0 of 8
Pressure switch
Thermostat
: Test volume
th
Feb 2019