cULus Zone Certifications:
Models that contain the Ex e increased safety (E-box) are not cULus Zone
certified and not suitable for use in Class, Zone locations. Only the following
models are certified: G-STR-120-D-x, G-STR-120-T-x, G-STR-230-D-x, G-STR-
230-T-x, G-STR-024-D-x, and G-STR-024-T-x. Please disregard any references
to the E-box when using these instructions for Class, Zone installations
Model numbers with suffix –21J (21 joule) use protections:
Class I, Zone 1, A Ex db IIC T3
Zone 21, AEx tb IIIC T3/200°C IP66 (Tamb= -55°C to +70°C)
Ex db IIC T3
Ex tb IIIC T3/200°C IP66 (Tamb= -55°C to +70°C)
Model numbers with suffix –15J (15 joule) are same as above except: Ex tb
IIIC T3/165°C IP66 (Tamb= -55°C to +70°C)
UL Fire Alarm Certifications:

Unpacking the Beacon

EXPLOSION HAZARD: A damaged lens can lead to explosions, causing
serious injury or death. If a lens is damaged, it must be replaced.
After unpacking the beacon, examine it for damage that may have occurred in
transit. If it has been damaged, do not attempt to install or operate it. File a claim
immediately with the carrier, stating the extent of the damage. Carefully check
all envelopes, shipping labels, and tags before removing or discarding them.
Disposal of all shipping materials must be carried out in accordance with national
and local codes and standards. If any parts are missing, please call Federal Signal
Customer Support at +1 708-534-4756 or +1 877-289-3246.

Creating Combination Fixtures in the Field

The Federal Signal Global Series Ex de products can be connected together
in the field using interchangeable E-box end caps and a proprietary coupling
system. The proprietary coupling system allows for simple, and cost effective,
wiring from product to product, often eliminating the need for expensive Ex
wiring practices and Ex rated glands. The E-box is available only when factory
installed on an Ex d unit or when used as a E-box spacer adjoining an existing
E-box. for available options, refer to the accessories listed on page 20. When
creating certain fixture combinations, it is necessary to replace the E-box end
caps before mounting the product. If you are creating combination fixtures, refer
to instruction manual 25500259 for specific instructions and details.
A note about combination fixtures: If the product is Ex db marked, it is for use
in gas atmospheres. If the product is Ex db e marked, it uses increased-safety
terminal enclosures and is for use in gas atmospheres. The product is Ex tb
marked for use in dust atmospheres.
Installation and Maintenance Instructions
(see page 21)
Model G-STR Global Series Strobe Beacon
7