Installation
From the PowerAlert Device Manager Interface, turn ON the cooling unit by
selecting the Control menu. Under the Control menu, check the "Turn On Device"
option and click the activation button to the right. Next, navigate to the
Configuration menu> Device Settings to ensure the E2MT sensor is selected.
Under the Function: Device Thresholds drop-down menu in the box labeled
"Value", type in the temperature set-point you wish the SRCOOLNET2LX to target
A
and press activation button to the right
B
. The set point control on the device
display panel will be overridden.
B
A