Installation
The cooling unit will now begin cooling when the temperature reading at E2MT
equals or exceeds the set point value you entered. When the temperature falls
below this set-point, the unit will stop cooling. If the "Always On" checkbox is
checked, the fans will remain running when the unit stops cooling. If the "Always
On" checkbox is unchecked, the fans will shut off and the unit will shut down. Once
the temperature reaches the set point again, the unit will restart and begin cooling
until the temperature reported by E2MT returns below the set point.
Note: This cycle will continue indefinitely until you select "Shutdown Cooler" from the
SRCOOLNET2LX user interface or turn the cooling unit off via the device display panel.
Important Considerations When Using Remote Temperature Setpoint
6-2
Mode
It is important to keep the following considerations in mind when using the
Remote Temperature Set-Point feature of SRCOOLNET2LX:
The temperature being used for controlling the attached cooling device is the
1
E2MT sensor, NOT the return air temperature. The return air temperature
may be higher or lower than the temperature E2MT is reporting.
The set point displayed on the attached cooling unit's display panel should
2
be ignored when the SRCOOLNET2LX is set to Remote Temperature Set-
Point mode in the PowerAlert Device Manager.* The set point displayed on
the device display panel will be the minimum (when cooling) or maximum
(when not cooling) set point permissible by the cooling unit.*
*The SRCOOL2KWM and compatible SRCOOL33K will display the correct set point on
the cooling unit's display.
Note: When the Remote Set-Point Temperature feature is enabled, the unit will show
as "EXTERNAL" on the SRCOOL33K's LCD display. If there is no setting of external
temperature set-point within 60 seconds, the unit will measure the value internally and
the icon "EXTERNAL" will be off.
If the power button on the cooling unit display panel is pressed while in
3
Remote Temperature Set-Point mode, the mode will be canceled.