LED Driver Installation
Best Practices Guide
EcoSystemT 5-Series/Hi-lumeR 1% EcoSystemT LED Driver
Driver Mounting
Mount driver flush against fixture to provide best heat transfer. Avoid mounting driver close to heat source such as the light source. Installer is responsible
for ensuring that the driver calibration point (t
Specification Submittal (LutronR P/N 369823) or the Hi-lumeR 1% EcoSystemT LED Driver Specification Submittal (Lutron
Stud Mounting
(Uses 8 – 32 Threaded Stud)
Correct
Incorrect
Installing or Servicing LED Driver or Light Engine
WARNING: Shock hazard. May result in serious injury or death.
Disconnect power before servicing or installing.
Driver Wiring
For proper wiring, follow wiring schematic on driver being installed. Driver photos are for reference only.
K Enclosure
3.00 in (76 mm) W × 1.00 in (25 mm) H × 4.90 in (124 mm) L
Power Wiring
LDE Models
K Enclosure
1
GND
NEU
Power Input
(Line Voltage)
N/C
L
EcoSystemT
E2
Digital Link
(Class 1 or
E1
Class 2)
2,3
1
All drivers can be grounded through the mounting tabs or studs. K-enclosure drivers may
be grounded by using the optional ground terminal.
2
Class 2 must be separated from Class 1 and line voltage wiring by the following: 0.25 in
(6 mm) or physical barrier. Please refer to Application Note #142 for further information.
3
EcoSystem
Digital Link length is limited by the wire gauge used for E1 and E2 as follows:
T
EcoSystemT Digital Link Wiring
Wire Gauge Digital Link Length (max)
18 AWG
550 ft
16 AWG
900 ft
14 AWG
1400 ft
12 AWG
2200 ft
Wire Size
Digital Link Length (max)
2
0.75 mm
155 m
1.0 mm
2
207 m
1.5 mm
2
310 m
2
2.5 mm
517 m
2
4.0 mm
828 m
To EcoSystem
Digital Link compatible devices
T
) does not exceed the maximum rated temperature. For more information, refer to the EcoSystemT 5-Series
c
K Enclosures
Driver must be electrically grounded for proper performance and to meet UL
K enclosure mounting tabs, grounding should be accomplished by using paint-piercing mounting hardware to ensure
electrical connection through driver enclosure and fixture.
M Enclosure
1.18 in (30 mm) W × 1.00 in (25 mm) H × 14.25 in (362 mm) L
M Enclosure
NEU
Power Input
N/C
(Line Voltage)
L
N/C
N/C
EcoSystemT
E2
Digital Link
(Class 1 or
E1
Class 2)
2,3
Tab Mounting
Load Wiring
Wire Gauge
18 AWG (0.75 mm
2
) 30 ft (9 m)
2
16 AWG (1.5 mm
)
2
14 AWG (2.5 mm
)
12 AWG (4.0 mm
2
)
Replacement of LED Driver
in the Field
WARNING: Risk of fire or electric shock. May result in serious injury
or death. LED Retrofit Kit installation requires knowledge of luminaires
electrical systems. If not qualified, do not attempt installation. Contact
a qualified electrician.
To prevent wiring damage or abrasion, do not expose wiring to edges
of sheet metal or other sharp objects.
Direct replacement LED drivers shall have the identical part number as the
Driver
driver being replaced.
terminals
THE RETROFIT ASSEMBLY IS ACCEPTED AS A COMPONENT OF A
LUMINAIRE WHERE THE SUITABILITY OF THE COMBINATION SHALL BE
DETERMINED BY UL OR AUTHORITIES HAVING JURISDICTION.
Lutron
Customer Assistance 1.844.LUTRON1 (1.844.588.7661)
®
)Lutron, Lutron, and Hi-lume are registered trademarks and EcoSystem is a trademark of Lutron
Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy,
Massachusetts. UL is a registered trademark of Underwriters Laboratories, Inc.
www.lutron.com
P/N 369832).
®
M Enclosure
and NEC
requirements. When using
®
®
Wire Strip Length
For all terminals.
5/16 in (8 mm)
Note: Class 2 output designed to withstand hot swap.
LED light source
See table below
Maximum Lead Length
150 mA –700 mA 710 mA –1.5 A 1.51 A –2.10 A
15 ft (4.5 m)
35 ft (10.5 m)
25 ft (7.5 m)
50 ft (15 m)
40 ft (12 m)
100 ft (30 m)
60 ft (18 m)
P/N 041542a
01/2016
Solid copper wire
18 –16 AWG
(0.75 –1.5 mm
2
)
–V (Black)
+V (Red)
10 ft (3 m)
15 ft (4.5 m)
25 ft (7.5 m)
40 ft (12 m)