Technical features
-
Fin spacing 7,0 mm
-
Capacity range: from 12,5 to 59,9 kW
-
Air flow rate: from 7930 to 43030 m
-
Operating temperature: from –25 to 40 °C
Hazards / Risks
1.
Electric shock. The model is equipped with fan
motors and electric defrost heaters. The
supply voltage is 400 V AC. It is important to
use electrical safety systems that are in com-
pliance to the regulations in force.
2.
Burns. The surface of the electric defrost hea-
ters can reach the temperature of 350 ° C.
3.
Cuts. The heat exchanger is made with fins
with sharp edges and the casing is made of
sheet metal parts.
4.
Parts in motion. The model is equipped with
fan motors fitted with external protection.
5.
Crushing. The weight of unit may exceed 270 kg.
Reference standards
-
MACHINES DIRECTIVE 2006/42/EC
-
LOW-VOLTAGE DIRECTIVE 2014/35/UE
-
ELECTROMAGNETIC COMPATIBILITY DIR. 2014/30/UE
-
PED DIRECTIVE 2014/68/UE
-
ERP DIRECTIVE 2009/125/EC
20