7.1.4
CSA Certification Record
Certificate:
Class 2258 04
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X:
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner
Input rated
Output pressure
Intrinsically safe with entity parameters of:
Terminals 11 / 12
Terminals 81 / 82
Terminals 83 / 84
Terminals 31 / 32
Terminals 41 / 42 and
51 / 52
Terminals Limit2 41 / 42 and
Limit1 51 / 52
When installed per installation Drawing No 901064
Temperature Code
Max. Ambient
IMPORTANT (NOTE)
•
The "x" in P/N denotes minor mechanical variations or optional features.
•
Local communication interface LKS shall not be used in hazardous location.
•
Each pair of conductors of each intrinsic safety circuit shall be shielded.
CI/TZIDC/110/120-ES
Datos técnicos relevantes de la protección Ex
V max = 30 V
I max = 104 mA
C
= 6.6 nF
i
L
= 0 uH
i
V max = 30 V
I max = 110 mA
C
= 3.7 nF
i
L
= 0 uH
i
V max = 30 V
I max = 96 mA
C
= 3.7 nF
i
L
= 0 uH
i
V max = 30 V
I max = 110 mA
C
= 6.6 nF
i
L
= 0 uH
i
V max = 30 V
I max = 96 mA
C
= 3.7 nF
i
L
= 0 uH
i
V max = 15.5 V
I max = 52 mA
C
= 20 nF
i
L
= 30 uH
i
TZIDC, TZIDC-110, TZIDC-120
1649904 (LR 20312)
PROCESS CONTROL EQUIPMENT –
Intrinsically Safe, Entity – For Hazardous
Locations
30 V DC; max.4 ... 20 mA
Max. 90 psi
T4
85 Deg C
37