PowPak
|
Installation
Programming without a Vive Hub
Dimming Module with 0 –10 V
Part of the Vive Family
Start Here
Associate Wireless Transmitters to
1
PowPak Dimming Module with 0 –10 V
Before beginning this step, make sure that there are no
other PowPak modules being set up within the same
building. It is possible that wireless transmitters from other
systems can be incorrectly associated to this module.
A On PowPak Dimming Module
with 0 –10 V, hold Toggle button
" u " for 6 seconds until lights
flash.
The Load Status LED will begin
flashing twice per second.
B Hold the indicated button on each transmitter for
6 seconds. Lights will flash to show that wireless
transmitters have been associated.
Link
C On PowPak Dimming Module with 0 –10 V, hold
Toggle button " u " for 6 seconds to save association.
Lights will flash and LED will quickly blink for
2 seconds.
D Permanently install wireless transmitters
(consult individual component installation guides for
information).
Reset Factory Defaults
Note: In some instances, it may be necessary to reset the
PowPak Dimming Module with 0 –10 V and connected
devices back to factory default settings. Before beginning,
make sure that all devices are connected and powered.
A Triple-tap the Toggle button " u " on the PowPak Dimming
Module with 0 –10 V and hold until the LED begins to flash
slowly; release button.
B Within 3 seconds of the start of flashing, triple-tap the same
button again and the LEDs will flash rapidly indicating that the
unit has been reset to factory defaults.
Note: Any associations or programming previously set
up with the PowPak will be erased and will need to be
re-programmed.
Lutron, Pico, and PowPak are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr and Vive are trademarks of Lutron Electronics Co., Inc. Safari is a trademark of Apple Inc., registered in the U.S. and other countries. Chrome is a trademark of Google Inc.
NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. ©2013 – 2017 Lutron Electronics Co., Inc.
Calibrate the Radio Powr Savr Daylight Sensor
2
Daylight Sensor will control all wired fixtures equally.
A Press and release the "Cal." button on the Daylight Sensor.
B Set lights in room to desired light level.
C Press and hold the "Cal." button for 6 seconds.
D Exit room for 5 minutes to complete calibration.
Note: When calibration has completed, all lights will flash and begin to respond to daylight.
Multiple Daylight Rows (Optional)
For every row of daylighting a separate PowPak Dimming Module with 0 –10 V must be used. For
detailed setup refer to the tuning section of the Radio Powr Savr Daylight Sensor installation guide.
• Select the PowPak Dimming Module with 0 –10 V that you want to adjust by pressing the toggle button.
Set a Favorite Light Level
3
(Optional)
For Pico remote controls with a Favorite Button.
A Adjust lights to desired level:
Use the Raise button " " or Lower button " " on the Pico remote
control.
B Save favorite level:
Press and hold the Favorite button for 6 seconds. The load will flash
3 times to confirm that the Favorite level is saved.
4
Set Low-End Trim and High-End Trim
For best results, minimize the amount of sunlight entering the room before performing the
Test
following procedures.
Notes
Depending on the fixture manufacturer or load, low-end trim and high-end trim may
need to be adjusted.
• Trim low-end to ensure a stable light level because some loads will flicker or drop out
if trimmed too low.
• Be sure that you can turn on the lights to the low-end trim level without any abnormal
operation.
• The factory default high-end trim is suitable for most applications but can be adjusted
as desired.
Low-End Trim
A Enter low-end trim adjustment mode:
Press and hold the Lower button " " on the fixture control for 12 seconds.
The lights will flash and the load status LED will begin flashing.
B Adjust the low-end trim:
Use the Raise button " " and Lower button " " on the fixture control to adjust and set the lights
to the desired low-end (1 to 45%).
C Save the low-end trim:
Press and hold the Toggle button
" u "
for 6 seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
High-End Trim
A Enter high-end trim adjustment mode:
Press and hold the Raise button " " on the fixture control for 12 seconds.
The lights will flash and the load status LED will flash.
B Adjust the high-end trim:
Use the Raise button " " and Lower button " " on the fixture control to adjust and set the lights
to the desired high-end (55 to 100%).
C Save the high-end trim:
Press and hold the Toggle button
" u "
for 6 seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
5
Link
Cal.
Test
A Enter minimum light level adjustment mode:
B Change the minimum light level:
C Save the minimum light level:
Raise
Lower
6
Favorite
A Set desired occupancy light levels:
B Save occupancy light levels:
(Optional)
Customer Assistance:
U.S.A. / Canada: 1.844.LUTRON1
United Kingdom: 0800.282.107
Europe: +44.(0)20.7680.4481
Mexico: +1.888.235.2910
Limited Warranty: www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
FCC / IC Information
This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following
two conditions: (1) This device may not cause interference, and (2) this device must accept any interference, including interference that may cause
undesired operation. Modifications not expressly approved by Lutron Electronics Co., Inc. could void the user's authority to operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct
the interference by one or more of the following measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Customer Assistance www.lutron.com/support
Set Minimum Light Level
(Optional)
Certain applications (e.g., hallways), may require that the lights never turn off. For these areas,
activate Minimum Light Level mode.
Press and hold Toggle button " u " and Lower button " " for 12 seconds. Lights will flash
high-low-high and LED will begin flashing.
If lights stop flashing and go to high-end, the minimum light level is set to OFF (default).
If lights stop flashing and go to low-end, the minimum light level is ON and set to low-end.
Press Raise button " " to set minimum light level to low-end.
Press Lower button " " to set minimum light level to OFF.
Press and hold Toggle button " u " for 6 seconds. LED will quickly flash to indicate that new level
has been saved.
Set Occupancy Light Levels
(Optional)
Note: Unoccupied light level is always the minimum light level and cannot be adjusted.
Use Raise/Lower buttons " / " on the PowPak Dimming Module with 0 –10 V or Raise/Lower
buttons " /
" on all associated Pico Remote Controls.
Press and hold Test button for 6 seconds on any associated Radio Powr Savr Occupancy Sensor
without a Lights On button. Release when Sensor lens starts to flash.
Or, press and hold Lights On button for 6 seconds on any associated Radio Powr Savr
Occupancy Sensor. Release when Sensor lens starts to flash.