Operating Conditions - WIKA IS-3 Suplemento Del Manual De Instrucciones

Ocultar thumbs Ver también para IS-3:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. Operating conditions

3. Operating conditions
All values apply at a mean ambient temperature of max. 40 °C and for the ambient ratings according
to SN 29500 standards.
The case of the pressure transmitter is undamaged.
EN
The pressure transmitter is not exposed to strong vibrations.
The process connection is suitable for the measuring range.
The wetted parts are suitable for the medium.
For safety applications, hydrogen is not permissible as a medium.
No pressure peaks.
No static pressures are higher than the values indicated in the data sheet.
Use a shielded cable grounded at least at one end.
The maximum measured error of -3.5 ... +10 % of span must be considered.
A measured value of < 3.8 mA and > 20.5 mA has to be interpreted as an error signal by the logic
unit.
The pressure transmitter is only suitable for pressure measurement in applications where the
pressure values change dynamically.
For the process industry, the following applies in addition:
Electromagnetic environment in accordance with EN 61326-1:2006, EN 61326-2-3:2006 and
EN 61326-3-2:2008.
Deviation to EN 61326-3-2:2008: Frequencies below 100 kHz not tested according to IEC 61000-4-6.
For machine-building applications, the following applies in addition:
Electromagnetic environment in accordance with EN 61326-1:2006, EN 61326-2-3:2006 and
EN 61326-3-1:2008.
In accordance with EN 61326-3-1:2008, for testing in accordance with IEC 61000-4-5, a test level
of 2 kV is required. The interference immunity of the IS-3 is 1 kV. To achieve a higher interference
immunity, external protective measures must be provided.
4
Addition to the operating instructions, model IS-3

Publicidad

Tabla de contenido
loading

Tabla de contenido