(2) Selection of circuit breaker and power cord:
Model
GMV-S120WL/A-S
GMV-S140WL/A-S
GMV-S160WL/A-S
NOTES!
① Selection of circuit breaker and power cord in the above table is based upon unit's maximum power
(maximum current). Power cord should be wire of H05RN-F or above.
② Specification of power cord is based on the working condition where ambient temperature is 40℃
and multi-core copper cable (working temperature is 90℃, e.g. power cable with YJV cross-linked
copper, insulated PE and PVC sheath) is lying on the surface of slot. If working condition changes,
please adjust the specification according to national standard.
③ Specification of circuit breaker is based on the working condition where ambient temperature of
circuit breaker is 40℃. If working condition changes, please adjust the specification according to
national standard.
5 Check Items after Installation and Test Operation
5.1 Check Items after Installation
Check items
Each part of the unit is installed securely?
Gas leakage test is taken or not?
Unit gets proper thermal insulation or not?
Drainage is smooth or not?
Is the voltage in accordance with the rated voltage
specified on the nameplate?
Is the electric wiring and pipe connection installed
correctly?
Unit is securely grounded or not?
Power cord meets the required specification?
Is the air inlet/outlet blocked?
Length of refrigerant pipe and the charging amount
of refrigerant are recorded or not?
Whether the fixing loop at the foot of compressor for
transportation is removed?
5.2 Test Run
NOTES!
① When the unit is installed for the first time and main board of outdoor unit is replaced, please conduct
test run. Otherwise, the unit can't operate.
② Test run must be conducted by professional person or under the guidance of professional person.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Circuit breaker
Power
capacity (A)
220V~ 50HZ
32
220V~ 50HZ
32
220V~ 50HZ
40
Unit may drop, shake or emit noise
Insufficient cooling (heating) capacity
Unit may have malfunction or components
Unit may have malfunction or components
Unit may have malfunction or components
The refrigerant charging amount is not
Number of ground
wire×Min sectional area
2
(mm
)
1×4.0
1×4.0
1×6.0
Possible conditions due to improper
installation
There may be condensate water.
There may be condensate water.
may get damaged.
may get damaged.
Electrical leakage
may get damaged.
Insufficient cooling (heating) capacity
accurate.
It may damage the compressor.
22
Number of power cord×Min
2
sectional area (mm
)
2×4.0
2×4.0
2×6.0
Check record