Troubleshooting - Endress+Hauser Solimotion FTR20 Instrucciones De Operación

Ocultar thumbs Ver también para Solimotion FTR20:
Tabla de contenido

Publicidad

en - Troubleshooting
64
Fault
Reason
Yellow LED off
No power or power too low
with bulk solids
(green LED does not light up)
in motion
Path of rays covered
(e.g. window dirty)
Wrong installation
Wrong settings
FTR20 defective
Yellow LED
FTR20 defective
always on
Strong
Turbulent application,
fluctuation of
reflections and so on
signal strength
Remedy
Check power supply
Check path of rays and clean
if necessary
Check installation
14
È
Check settings
44
È
Replace device or electronics
Replace device or electronics
Increase signal damping
57
È
Endress+Hauser

Publicidad

Tabla de contenido
loading