EAS ELECTRIC ETHKH160 Manual De Instrucciones página 85

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

1 DHW MODE SETTING
1.1. DHW MODE
1.2. TANK HEATER
1.3. DISINFECT
1.4. DHW PRIORITY
1.5. DHW PUMP
ENTER
OK
Using◄、► to scroll and use OK to enter,when the curson
is on
YES, press OK to set the DHW MODE effective.When
the cursor is on
NON,press OK to set the DHW MODE ineffective.
1. Go to MENU> FOR SERVICEMAN>DHW MODE SETTING>1.1
DHW MODE
1.1 DHW MODE
dT5_ON
dT1S5
T4DHWMAX
T4DHWMIN
t INTERVAL DHW
SCROLL
Use ◄、►、▼、▲ to scroll and adjust parameters,use BACK to exit.
dT5_ON is the temperature difference for starting the heat pump,
the picture below illustrate the function of dT5_ON.
T5
T5S
T5S-dT_ON
OFF
ON
compressor
T5S is target temperature of domestic hot water. T5 is actual
temperature of domestic hot water. When T5 drops to a certain
temperature(T5≤T5S-dT5_ON) , the heat pump will be available.
dT1S5 is the correct value for the target outlet water
temperature(T1S=T5+dT1S5)
T4DHWMAX is the maximum ambient temperature that the heat
pump can operate for domestic water heating, the unit will not operate
if the ambient temperature is above it in DHW mode.
T4DHWMIN is the minimum ambient temperature that the heat
pump can operate for domestic water heating, the heat pump will
turn off if the ambient temperature drop below it in water heating mode.
The relationship between operation of the unit and ambient
temperature can be illustrated in the picture below:
heat by TBH or AHS
T4DHWMIN
t_INTERVAL_DHW is the start time interval of compressor in DHW
mode. When the compressor stops running, the next time that the
compressor turn on should be " t_INTERVAL_DHW " minute later
at least.
YES
NON
YES
NON
YES
NON
YES
NON
YES
NON
SCROLL
5 °C
10°C
43°C
-10°C
5 MIN
OFF
heat by heat pump
OFF
T4DHWMAX
Go to FOR SERVICEMAN>DHW MODE SETTING>1.2
TANK HEATER
1.2 TANK HEATER
dT5 TBH OFF
T4_TBH_ON
t_TBH_DELAY
Use ◄、►、▼、▲ to scroll and adjust parameters. Use
BACK to exit.
dT5_TBH_OFF is the temperature difference between T5 and T5S
that turn the booster heater off, the booster heater will turn off if
T5≥T5S+dT_TBH_OFF, when the heat pump macfunction.
T4_TBH_ON is the temperature only when the ambient temperature
lower than it the booster heater will be available.
t_TBH_DELAY is the time that the compressor has run before
starting the booster heater(if T5<min(T5S,T5stop)).
The operation of the unit during DHW mode described in the picture
below:
T5S+dT5_TBH_OFF
T5stop
min(T5S,T5stop)-dT5_on
COMP.
In the picture, T5stop is a parameter relate to ambient temperature,
which can't be changed in the user interface, when T5≥T5stop, the
heat pump will turn off.
t
Note: the booster heater and backup heater can't operate
simultaneously, if the booster heater has been on, the backup
heater will be off.
If the booster heater is unavailable(1.2 TANK HEATER NON is
selected),the dT5_ON can't be adjusted and fixed at 2.
3. Go to MENU> FOR SERVICEMAN>DHW MODE SETTING>1.3
DISINFECT
1.3 DISINFECT
T5S_DI
t_DI_HIGHTMEP.
t_DI_MAX
T4
Use ◄、►、▼、▲ to scroll and adjust parameters. Use
BACK to exit.
T5S_DI is the target temperature of water in the domestic hot water
tank in DISINFECT function.
t_DI_HIGHTEMP. is the time that high temperature of water to be
lasted.
t_DI_MAX is the time that disinfection to be lasted, the change of the
domestic water temperature described in the picture below:
33
5 °C
20°C
90 MIN
SCROLL
T5
T5S
ON
OFF
ON
OFF
TBH
t_TBH_delay
5 °C
30 MIN
120 MIN
SCROLL
OFF
Time
V.1