EAS ELECTRIC ETHKH160 Manual De Instrucciones página 91

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6.19 TEST RUN
■ About TEST RUN
The TEST RUN is used to check correct operation of the values,
air purge, circulted pump running,cooling, heating and domestic
water heating
■ How to enter the TEST RUN
To enter the test run, go to MENU> FOR SERVICEMAN> TEST
RUN. Press OK. The following page will appear:
12 TEST RUN
Active the settings and
active the "TEST RUN"?
NO
CONFIRM
OK
If YES is selected, the following page will appear:
12 TEST RUN
12.1 POINT CHECK
AIR PURGE
CIRCULATED PUMP RUNNING
COOL MODE RUNNING
HEAT MODE RUNNING
DHW MODE RUNNING
ENTER
OK
Using
▼、▲ to scroll to the mode you want to run and press OK,
then the unit will run as you selected.
If 12.1 POINT CHECK is selected,the following page will disappear
12.1 PIONT CHECK
3-WAY VALVE
2-WAY VALVE
PUMP1
PUMP0
PUMP0
PUMPSOLAR
SCROLL
ON/OFF
ON/OFF
Using ▼、▲ to scroll to the components you want to check and press
ON/OFF, for example, when 3-WAY VALUE is selected and ON/OFF
pressed, if the 3-way value is open/close, then the operation of
3-way value is normal, so does other components.
If you select AIR PURGE and OK is pressed, the page will displayed
as following:
12 TEST RUN
Test run is on.
air purge is on.
CONFIRM
OK
When in air purge mode, the 3-way value will open, the 2-way value
will close, 60s later the pump in the unit(PUMPI) will operate for
10min, during which the flow switch will not work. after the pump
stoped, the 3-way value will close and the 2-way value will open, 60s
later both the PUMPI and PUMPO will operate until the next
command recived.
YES
SCROLL
SCROLL
12.1 PIONT CHECK
OFF
PUMPDHW
OFF
BACKUP HEATER1
OFF
BACKUP HEATER2
OFF
TANK HEATER
OFF
OFF
SCROLL
ON/OFF
ON/OFF
When the CIRCULATED PUMP RUNNING is selected, the page will
displayed as following:
12 TEST RUN
Test run is on.
Ciroulated pump is on.
When circulated pump running is turned on, all the running
components will stop, 60min later,the 3-way value will open, the
2-way value will close, 60s later PUMPI will operate , 30s later, if the
flow switch checked normal flow,the PUMPI will operate for 3min,
after the pump stoped, the 3-way value will close and the 2-way
value will open, 60s later the both PUMPI and PUMPO will operate,
2min later, the flow switch will check the water flow , if the flow switch
close for 15s, the PUMPI and PUMPO will operate until the next
command recived.
When the COOL MODE RUNNING is selected, the page will
displayed as following:
12 TEST RUN
Test run is on.
Cool mode is on.
Leaving water temperature is
15 °C.
During COOL MODE test running, the default target outlet water
temperature is 7°C, the unit will operate until the water temperature
drop to a certain value or the next command recived.
When the HEAT MODE RUNNING is selected, the page will
displayed as following:
OFF
OFF
12 TEST RUN
OFF
OFF
Test run is on.
Heat mode is on.
Leaving water temperature is
15 °C.
During HEAT MODE test running, the default target outlet water
temperature is 35°C, the first backup heater will turn on after the
compressor runned for 10min, 60s later the second backup heater
will turn on. After the two backup heater runned for 3min, both
backup heater will turn off, the heat pump will operate until the water
temperature increase to a certain value or the next command recived.
When the DHW MODE RUNNING is selected, the page will
displayed as following:
12 TEST RUN
Test run is on.
DHW mode is on.
Water flow temper. is 45°C
Water tank temper. is 30°C
During DHW MODE test running, the default target temperature of
the domestic water is 55°C, the booster heater will turn on after the
compressor runned for 10min, the booster heater will turn off 3min
later, the heat pump will operate until the water temperature increase
to a certain value or the next command recived.
39
CONFIRM
OK
CONFIRM
OK
CONFIRM
OK
CONFIRM
OK
V.1

Publicidad

Capítulos

Tabla de contenido
loading

Tabla de contenido