MD201 MB
a pressure gauge and a pressure switch
and is therefore suited to control pressure
differentials of filters used in cleanroom
and climate technology. The MD201 MB
instruments feature a high reading ac-
curacy and repeatability. They can be
used in negative pressure and/or over-
pressure conditions. This is essential
Technical data
Media compatibility
air or non-corrosive gases
Measuring ranges*
refer to data table
Measuring accuracy
± 2.0 % of full scale
Max. permissible pressure
70 kPa
Max. lowest pressure limit
–68 kPa (recommended)
Max. permissible temperature
–20 to +65 °C
Pressure connection
two pressure probes for plastic tubing 4 x 6/8 mm
Electrical connection
screw clamps with a cable gland M16
Microswitch
one SPDT contact 230/480 V at 50 Hz, 5A
Protection class
IP 54 (on request IP 65)
Dimensions of housing
200 x 120 x 90 mm (HxWxD)
Weight
~ 1 kg
Standard types
Type
Measuring range*
MD 201– 3 MB
0–300 Pa
MD 201– 5 MB
0–500 Pa
MD 201–10 MB
0–1.0 kPa
MD 201–15 MB
0–1.5 kPa
MD 201–30 MB
0–3.0 kPa
MD 201–50 MB
0–5.0 kPa
* other measuring/indicating and adjusting ranges on request
05/09
Differential pressure measuring instrument
with analogue scale and one switch-over contact for
filter control
The well-proven MD201 MB combines
for air halls or research/experimental
laboratories which for safety reasons
need to be kept above or below at-
mospheric pressure level. Differential
pressure gauge and switch are as-
sembled in a bi-partite, weather-proof
and shock-resistant plastic housing
and are ready for connection. The de-
vice needs almost no maintenance,
Adjusting range*
40–300 Pa
100–1000 Pa
0.1–1.0 kPa
0.3–5.0 kPa
0.3–5.0 kPa
0.3–5.0 kPa
as it works without any manometer fluids.
After opening the housing, the switching
point can be set at each individual dif-
ferential pressure switch (alternatively for
rising or falling pressure) by means of the
adjusting knob with scale. Due to its high
reading accuracy, the integrated differen-
tial pressure gauge can also be used for
pre-setting the switching point.
circuit diagram MD 201 MB
P
1 NC normally closed
3 COM common
2 NO normally open
PE - grounding wire
four assebly bores in the rear casing part
for cylinder head bolts M4
pressure connetion
two pressure probes for
plastic tubing 4 x 6/8 mm
blue for higher pressure (+)
black for lower pressure (–)
Switch-back difference
20 Pa
40 Pa
40 Pa
100 Pa
100 Pa
100 Pa
Briem
Steuerungstechnik GmbH
Lauterstraße 23
D-72622 Nürtingen
Phone +49 (0)70 22-60 92-0
Fax +49 (0)70 22-60 92-60
info@briem.de
www.briem.de
MD 201MB
7