◆ Check the oil level. Maintain the oil level between the "ADD" and the "FULL" mark
on the oil level gauge.
◆ Maintain the coolant level within 30 mm of the bottom of the filler pipe.
◆ Observe the air cleaner service indicator (if equipped). Service the air cleaner
when the yellow diaphragm enters the red zone or the red piston locks in the
visible position.
◆ Remove any electrical loads.
3.6.2 Engine Starting
The startup modes of the engine mainly include automatic mode and manual
mode. Please refer to the relevant controller manual for detailed information.
3.6.3 Cold Weather Starting
Do not use ether (starting fluids) unless specifically instructed to do so. Do not use
ether if the engine is equipped with an air inlet heater (electrically or fuel ignited
manifold heater). The use could cause personal injury and/or engine damage.
The use of jacket water heater can improve the engine startability at temperature
below 10℃(50℉). This can help reduce white smoke and misfire during startup in cold
weather.
3.6.4 After Starting Engine
Check the abnormal noise or vibration of the generator set.
Check the leakage of the exhaust system.
Monitor the generator set operation by way of the control module.
Check the engine temperature and oil pressure. The oil pressure must reach the
normal value after normal running of the generator set.
Monitor the outlet voltage and frequency of the generator set.
If not equipped with jacket water heater, operate the generator set at no-load for 8
minutes before applying the load (manual mode).
3.6.5 Loading the Generator Set
The power rating (kW) on the generator set nameplate determines how much
electrical load (motors, fans, heaters, air conditioners, appliances, etc.) the generator
set can power. If the sum of the concurrent electrical loads exceeds the rating power
of the generator set, the generator will shut down or the circuit breaker will trip. Each
phase of the generator set should carry the same load. If one phase current exceeds
the nameplate amperage, the electrical unbalance will cause electrical overload and
overheating.
When a large motor or air conditioner is started or cycles on and then on again,
even if the total electrical loads is less than the power rating of the generator set. It
is because that the startup load is much bigger than its running load.
WARNING
CAUTION
21