Pipes For Light Oil Burner - baltur BT 40G Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

GRAVITY SUPPLY SYSTEM
DROP-TYPE SYSTEM WITH SUPPLY FROM THE TANK TOP
SUCTION - TYPE FEEDING SYSTEM
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
10 Bottom valve
16
PIPES FOR LIGHT OIL BURNER MODEL
1 Tank
2 Feeding pipe
3 Wire-net filter
4 Pump
5 Degasifier
Pump axis
1 Tank
3 Wire-net filter
4 Pump
6 Suction pipe
7 Return pipe
Pump axis
Pump axis
N.B. For any missing devices in the piping, follow existing regulations.
H = Difference in level between level in the tank and the pump axis.
L = Maximum length of suction pipe including the vertical lift.
For each bend or valve deduct 0,25 m.
6 Suction pipe
7 Return pipe
8 Automatic fuel interception device at
burner shut off
9 Non-return valve
H
Total meters
meters
meters
Ø i. 10 mm.
0,5
20
1
20
1,5
25
2
25
2,5
30
3
30
8 Automatic fuel interception device
at burner shut off
9 Non-return valve
10 Bottom valve
H
Total meters
meters
meters
Ø i. 10 mm.
0,5
20
1
20
1,5
25
2
25
2,5
30
3
30
P = 3,5 m. (max.)
H
Total meters
meters
meters
Ø i. 10 mm.
0,5
17
1
14
1,5
11
2
9
2,5
7
3
4,5
3,5
-
Ø i. 12 mm.
30
30
35
35
40
40
Ø i. 12 mm.
30
30
35
35
40
40
Ø i. 12 mm.
24
21
18
15
13
9
-

Publicidad