NON-SERIOUS ALARMS
Thermostat OFF
■ Code A03 = water sensor error
■ Code A04 = remote humidity probe error (only if a remote
temperature probe is installed)
■ Code A05 = internal humidity probe error
N.B.: the alarm code is displayed only when the thermostat
is switched off
MODBUS
The protocol implemented in the controller is Modbus RTU
(9600, N, 8, 2) on RS485
FUNCTIONS IMPLEMENTED
■ 0x03 : Read Holding Registers
■ 0x04 : Read Input Registers
■ 0x10 : Write Multiple registers
EXCEPTIONS IMPLEMENTED
Exception Code 02: Invalidate data address
LIST OF SUPERVISION PARAMETERS
ADDRESS
REGISTER
Status
0
Speeds
1
Air temperature
2
3
Humidity
Water temperature
4
P00: Confi guration
5
P05: Confi g. DIN
6
T. Active setpoint
7
8
T. User setpoint
LCD version
9
Digital 1
50
-
51
52
Setpoint - Cooling
Setpoint - Heating
53
Minimum Setpoint – Cool.
54
Maximum Setpoint – Cool.
55
Minimum Setpoint – Heat.
56
57
Maximum Setpoint – Heat.
Speeds
58
Economy Correction
59
FWEC2
Advanced electronic controller
FC66002764
All manuals and user guides at all-guides.com
DESCRIPTION OF READ-ONLY REGISTERS [R]
■ "Staus" "REGISTER"
Thermostat ON
-
-
-
-
-
-
-
-
-
-
-
-
-
-
■ "SPEED" REGISTER: current operating speed of the
-
-
TYPE
U.M.
-
R
-
-
-
R
-
■ "AIR TEMPERATURE" REGISTER: room temperature
R
[°C/10]
R
%
R
[°C/10]
R
-
■ "HUMIDITY" REGISTER: room humidity read by the
R
-
R
[°C/10]
■ "WATER TEMPERATURE" REGISTER: value read by the
R
[°C/10]
■ "P00" Register: "Controller confi guration" parameter
R
-
■ "T. ACTIVE SETPOINT" Register: setpoint used for tem-
■ "T. USER SETPOINT" Register: setpoint programmed by
R/W
-
R/W
-
R/W
[°C/10]
■ "LCD VERSION" Register : defi nes the controller type and
R/W
[°C/10]
R/W
[°C/10]
R/W
[°C/10]
R/W
[°C/10]
R/W
[°C/10]
R/W
-
R/W
[°C/10]
H
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
-
-
P04
Deum
P06
L
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Vh
Vc
Alarm
MinT
Eco
On/Off: unit status (0: Off, 1=On)
S/W: operation mode (0: S=cooling,1:W=heating)
P01: "on unit/wall-mounted" parameter
Eco: Economy logic active
Min.T: Minimum Temperature logic selected
Alarm: general alarm indication (activated when any of
the managed alarms is triggered)
Vc: status of digital output Vc
Vh: status of digital output Vh
DI1: logical value of dig. input 1 (the physical status of the
input depends on the associated logic)
DI2: logical value of dig. input 2 (the physical status of the
input depends on the associated logic)
P07: "DIN 2 Logic" parameter
P06: "DIN 1 Logic" parameter
Dehum: dehumidifi cation ON (0:no, 1:yes)
P04: "water probe present" parameter
indoor unit
0: fan OFF
1: extra-low speed
2: low speed
3: medium speed
4: high speed
read by the controller and shown on the display (N.B.:
this temperature corresponds to the reading of the remote
probe if the controller is located on the unit, or the read-
ing of the internal probe in the case of a wall-mounted
controller and remote probe disconnected)
controller via the probe associated with the temperature
probe used
water probe (SW)
perature control
the user (it may differ from the active setpoint due to cor-
rections based on economy logics,...or use of the setpoint
imposed by the supervision software)
software version installed (0xHHSS: HH: ASCII character,
SS:sw version)
Bit 10
Bit 9
Bit 8
P07
DI2
DI1
Bit 2
Bit 1
Bit 0
P01
S/W
On/Off
Installation and operation manual
9