Supply Voltage.
Supply voltage depending on model:
85 – 265 V AC, 50/60 Hz. Maximum power consumption: 20 V A
20 – 60 V DC and 24 V AC ± 15% 50/60 Hz , Maximum power
consumption: 10 W, 17 V A.
Modbus
It is important that the installation of the data communication
cable be done correctly. Cf. separate literature No. RC8AC.
Remember termination at the bus termination.
DO - Digital outputs, 8 pcs. DO1 - DO8
Function defined via the HMI in the parameter list
DO1, DO2
- Normally Open contact,
10 A 250 V AC for resistive loads
3.5 A 230 V AC for inductive loads
DO3, DO4,DO7, DO8:
- Changeover Contact,
6 A 250 V AC for resistive loads
4 A 250 V AC for inductive loads
DO5,DO6:
- Solid state relays,
Imax. = 0.5A
Imin. = 50 mA.
Leakage<1.5 mA
Not short-circuit protected
OBSERVE: AC only
AO - Analogue output, 4 pcs. AO1,AO2,AO3,AO4
Function defined via the HMI in the parameter list.
AO1, AO2:
0 / 10 V DC 10 mA max for each output
AO3, AO4:
Optoinsulated. 0 / 10 V DC 10 mA max for each output
External power supply 24 V a.c / 24 V d.c
OBSERVE:
Connect 24 V on N and L (separate supply). Avoid earth fault
current. Use double-insulated transformer. The secondary side
must not be earthed.
Obtain 0-10 volts from terminals N and AO3, respectively N and
AO4.
PAY ATTENTION TO THE POLARITY of N.
AKS 32R
AKS 32
AKS 33
© Danfoss | DCS (vt) | 2019.05
AI - Analogue inputs, 4 pcs. AI1 - AI4
DI - Digital inputs, 8 pcs. DI1 - DI8
AI - Analogue inputs, 4 pcs. AI5 - AI8
10-90% ratiometric
1-5 V
0-20mA
4-20mA
Function defined via the HMI in the parameter list
Pressure transmitters
• Ratiometric: 10-90% of supply, AKS 32R
1-5 V, AKS 32
0-20 mA / 4-20 mA, AKS 33 (supply = 12 V)
Temperature sensor
• Pt 1000 ohm, AKS 11 or AKS 21.
• NTC 86K ohm @ 25°C, from digital scroll.
The connection may be a shut-down or interruption function.
Select what is to be activated during configuration.
Function defined via the HMI in the parameter list
Pressure transmitters
• Ratiometric: 10-90% of supply, AKS 32R
1-5 V, AKS 32
Temperature sensor
• Pt 1000 ohm, AKS 11 or AKS 21.
• NTC 86K ohm @ 25°C, from digital scroll.
AN30561784681801-000101 | 3