ELECTRICAL CONNECTION
INSTRUCTIONS
Step 1. Provide electrical service according
to your local electrical code to the junction
box located on the plaster ring. Supply wire
insulation must be rated for at least 90˚C.
Step 2. Strip supply wires 3/8" and insert into
appropriate connectors. Connect black fixture
wire to hot, white fixture wire to neutral and
green fixture wire to ground.
For 0-10V dimming, connect violet (+) and
gray (-) dimmer wires.
FIXTURE DIMMING
Fixtures are dimmable with most 0-10V wall
box dimmers. Consult Juno Product Services
or
website
for compatibility.
1300 South Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • www.junolightinggroup.com
INSTALLATION INSTRUCTIONS
with Universal Driver (-U Option)
Commercial Recessed Housing
EMERGENCY BATTERY BACK UP
WITH REMOTE TEST SWITCH
(BR OPTION)
When the fixture is ordered with the emergency
battery back up option (BR), the housing comes
from the factory with the battery pack already
wired to the fixture and a carton with the test
switch accessories (shipped in same carton
as housing).
Step 1. Provide electrical service according
to your local electrical code to the junction
box located on the plaster ring. Supply wire
insulation must be rated for at least 90˚C.
Note: For proper charging and function
of emergency battery, an unswitched hot
conductor must be connected to the battery
independent of the driver power.
Power for fixture and battery charging must
be from the same branch circuit.
Step 2. Refer to the instruction manual
provided by the battery manufacturer located in
the carton with the test accessories to complete
wiring and installation of emergency fixture and
test switch.
DRIVER REPLACEMENT
Driver replacements must be performed by a
qualified electrician. Remove inner housing
from fixture to access driver. Order replacement
kits as identified on the driver. The replacement
kits include detailed instructions for driver
replacement.
TC LED Downlights
TRIM INSTALLATION
After ceiling is finished and painted, remove
paint shield from fixture. Discard or recycle.
To install trims using COIL SPRINGS remove
OPTIC REFLECTOR by rotating 1/4 turn
counter-clockwise (Fig. 5). Connect trim springs
to fixture L-brackets as shown (Fig. 6).
Take note of flange details at top of OPTIC
REFLECTOR, align and insert in fixture and
rotate 1/4 turn clockwise until it stops.
To install trims with TORSION SPRINGS:
For lensed trims, it is not necessary to remove
OPTIC REFLECTOR. For lensed trims
equipped with an internal reflector, remove
the reflector supplied with the trim and discard
or recycle.
For hyperbolic trims, follow instructions provided
with the trim.
L-Bracket
© 2016 Acuity Brands Lighting, Inc.
Optic
Reflector
Figure 5
Coil
Spring
Figure 6
Rev 4/15
P5890
pg 2 of 2