The radio receiver in this product is compatible only with the new ARC (Advanced Rolling Code) transmitters which, thanks to 128-bit encryption ensure
superior copy-security.
Storing new ARC transmitters is quite similar to that of normal rolling code transmitters with HCS coding
1) LOGICA CONTROL UNIT
1.1) WIRE DIAGRAM
Wire connections shown in Fig. 1 are described hereunder:
Terminal
Function
L-N-GND
Power supply
BLINK
Flashing light
MOT-COM-MOT
Motor 1/2
SER L
Service light
COM
COM
SW1
SWO
SW2
SWC
STOP
STOP
PHOT
PHOT
CLOSE
CLOSE
PP
Step-by-Step
24 Vac
24 Vac
AUX
AUX
BAR
COSTA
ANT-SHIELD
Aerial
CM-CM
Capacitor
J2
Radio receiver
ENC1
Encoder
Primary
MF3/8/4
Transformer
J6
N/A
Secondary
MF7/MF5/MF6
Transformer
Should two motors be used, connect the limit switches of one single motor to the control unit.
The connection between 1 motor ZED.AUTR and 1 motor ZED.SC is shown in Fig.3.
The connection between 1 external control unit (LOGICA 7B) and 2 motors ZED.SC is shown in Fig.4.
1.2) FUSES
F1
Output protection fuse of accessories and signals (T500mA)
F3
Motor protection fuse (F5A)
1.3) TO ADJUST THE MOTOR POWER
WARNING! This adjustment affects the safety level of the automatic system.
Check that the thrust applied onto the wing complies with regulations in force.
On the power supply transformer, a Faston connector (T1) is provided which allows to adjust motor power to 4 different levels. By positioning the Faston
(T1) on 120, the minimum power is obtained, by moving the Faston to 210 the maximum power is obtained.
ARC CONTROL UNIT
IMPORTANT, PLEASE READ CAREFULLY:
Description
Input, 230VAC 50Hz (1-Phase/2-Neutral)
Connection of flashing light, 230Vac 40W max.
Connection to motor 1/2 : (6-speed/7-Com/8-speed)*
Should 2 motors be used, connect the second motor in parallel.
Connection to the courtesy light 24Vdc (LED.ZED accessory or LED.SC panel connection).
Common for limit switch and all control inputs.
Input, OPEN limit switch (N.C. contact)
Input, CLOSE limit switch (N.C. contact)
Input, STOP push button (N.C. contact)
Input, connection to safety devices, N.C. contact
(e.g. Photocells)
Input, CLOSE push button (N.O. contact)
Input, step-by-step push button (N.O. contact)
Output, power supply of accessories, 24Vac/1A max.
Normally Open (N.O.) contact, not powered, configurable as SCA/II°CH/PHOTO TEST.
Input, safety edge contact
Resistive edge: Closed "DAS" jumper
Mechanical edge: Open "DAS" jumper
If the safety edge is activated in the opening phase, the gate stops.
In the closing phase, the gate stops and the performs a movement reversion (opens) for 3s.
Connection to the radio receiver card of the aerial (SHIELD-screen/A NT-signal).
Connected to motor capacitor
Built-in radio receiver.
The radio receiver in this product is compatible with the ARC (Advanced Rolling Code) transmitters, with
433.92 MHz frequency.
Fast connector for encoder connection (ZED Encoder version only)
Connection, winding of primary transformer
Warning: The Faston on the transformer connected to terminal MF8 (TORQ) set the torque applied to
motor.
See section "To adjust the motor power ".
Not available
Connection, winding of secondary transformer
IMPORTANT: