Pressure Sensors with IO-Link
BSP-B... /-V...
Menu functions for sensors with 2 switching points
First menu level
Menu 1 – Setting for switching point 1 Setting
SP 1
for the relevant value from which switching
FH 1
point 1 is activated.
If the window function in menu 5:6 is activated,
the value for switching point 1 represents the
upper pressure limit in the window (FH).
Menu 2 – Setting for return point 1 Setting for
rP 1
the relevant value from which return point 1 is
FL 1
activated.
If the window function in menu 5:6 is activated,
the return value for switching point 1 represents
the lower pressure limit in the window (FL).
Menu 3* – Setting for switching point 2 Setting
SP 2
for the relevant value from which switching
FH 2
point 2 is activated.
If the window function in menu 5:7 is activated,
the value for switching point 2 represents the
upper pressure limit in the window.
Menu 4* – Setting for return point 2 Setting for
rP 2
the relevant value from which return point 2 is
FL 2
activated.
If the window function in menu 5:7 is activated,
the return value for switching point 2 represents
the lower pressure limit in the window.
Menu 5 – Extended functions
EF
Second menu level
Menu 5:1 – Reset
rES
Restores all adjustable parameters to their
default settings and deletes the Min. and Max.
values
Menu 5:2 – Switching delay time 1
dS 1
Setting for the value of switching delay time 1,
which starts after switching point 1 is reached
(time range 0...50 seconds)
Menu 5:3 – Return switching delay time 1
dr 1
Setting for the value of return switching delay
time 1, which starts after return point 1 is
reached (time range 0...50 seconds)
*
dS 2
Menu 5:4
– Switching delay time 2
Setting for the value of switching delay time 2,
which starts after switching point 2 is reached
(time range 0...50 seconds)
*
dr 2
Menu 5:5
– Return switching delay time 2
Setting for the value of return switching delay
time 2, which starts after return point 2 is
reached (time range 0...50 seconds)
Menu 5:6 – Output 1
ou 1
Switching function of the switching output:
= Hysteresis function, NO contact
Hno
= Hysteresis function, NC contact
Hnc
= Window function, NO contact
Fno
= Window function, NC contact
Fnc
www.balluff.com
Menu functions (continued)
Second menu level (continued)
*
ou 2
Menu 5:7
– Output 2
Switching function of the switching output:
= Hysteresis function, NO contact
Hno
= Hysteresis function, NC contact
Hnc
= Window function, NO contact
Fno
= Window function, NC contact
Fnc
Menu 5:8 Switching units
uni
Selection of physical measuring unit for the
displayed and configured pressure value:
= bar,
bAr
= mbar,
nnBa
= PSI,
PSi
= MPa
mPA
Menu 5:9 – Rotate display
FLiP
Rotate the display 180°
Menu 5:10 - Min. value
Lo
Display of minimum pressure attained during
the measurement (the value is lost when the
power supply is interrupted)
Menu 5:11 - Max. value
Hi
Display of maximum pressure attained during
the measurement (the value is lost when the
power supply is interrupted)
Menu 5:12 – Deletion of Min and Max values
---
The display confirms that the process for
deleting the values has started
Menu 5:13 – Neutral point adjustments
SET0
Correction for the neutral point of the display
and of the analog output signal to up to
+/– 3% of the nominal pressure range
Menu 5:14 – Measure value damping
dAP
Configuration of the measure value damping
value (0...1000 ms in 10 ms increments)
Menu 5:15 – Access protection
codE
Setting the password for protecting access to
the menu
0000 = no password
0000...9999 adjustable
Legend
*
Menus marked with an asterisk
do not appear if the sensor has
an analog output.
English