Technical Data; Ambient Conditions - Balluff BSP B S1B Serie Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Pressure Sensors with IO-Link
BSP-B... /-V...

Technical data

Electrical data
Supply voltage U
S
Output current max.
Interface
No-load supply current I
0
Reverse polarity protected
Short-circuit protected
Switching frequency f
Accuracy according to IEC 60770 ≤ ±0.5% FSO BFSL
Temperature error
BSP standard, high-end and
flush-mounted starting at 100 bar
BSP flush-mounted up to 50 bar
Mechanical data
Housing material
BSP standard sensors
BSP high-end sensors
Measuring cell material
Sealing ring material
Plug connector socket
Process connection
BSP standard, high-end
BSP flush-mounted high-end
Displays
Function indicators
Display

Ambient conditions

Ambient temperature range
BSP standard sensors
BSP high-end sensors
Material temperature
BSP standard sensors
BSP high-end sensors
Degree of protection as per
IEC 60529
Your pressure sensor type
The type plate contains the exact designation and most
important technical data so that the device can be identi-
fied clearly.
Ordering code
Electr. connections
12
English
18...36 V DC
250 mA
IO-Link V1.1
max.
≤ 50 mA
Yes
Yes
200 Hz
≤ ±0.3% FSO/10 K
.
≤ ±0.15% FSO/10 K
PA 6.6, stainless steel
Stainless steel
Ceramic
Fluoroelastomer
M12, 4-pin
G 1/4", 1/4" NPT
G 1/2" flush-mounted
LEDs
7-segment display
–25...+85 °C
–40...+85 °C
–25...+125 °C
–40...+125 °C
IP 67 when connected
Part number
Nominal pressure
Pressure data
BSP, not
flush-mounted
Relative nominal
pressure
Sensor –1...2 bar
2 bar
Sensor –1...10 bar
10 bar
Sensor 0...2 bar
2 bar
Sensor 0...5 bar
5 bar
Sensor 0...10 bar
10 bar
Sensor 0...20 bar
20 bar
Sensor 0...50 bar
50 bar
Sensor 0...100 bar
100 bar
Sensor 0...250 bar
250 bar
Sensor 0...400 bar
400 bar
Sensor 0...600 bar
600 bar
Overload pressure
Sensor –1...2 bar
4 bar
Sensor –1...10 bar
20 bar
Sensor 0...2 bar
4 bar
Sensor 0...5 bar
10 bar
Sensor 0...10 bar
20 bar
Sensor 0...20 bar
40 bar
Sensor 0...50 bar
100 bar
Sensor 0...100 bar
200 bar
Sensor 0...250 bar
400 bar
Sensor 0...400 bar
650 bar
Sensor 0...600 bar
750 bar
Cracking pressure
Sensor –1...2 bar
10 bar
Sensor –1...10 bar
35 bar
Sensor 0...2 bar
10 bar
Sensor 0...5 bar
15 bar
Sensor 0...10 bar
35 bar
Sensor 0...20 bar
75 bar
Sensor 0...50 bar
150 bar
Sensor 0...100 bar
200 bar
Sensor 0...250 bar
450 bar
Sensor 0...400 bar
700 bar
Sensor 0...600 bar
800 bar
Permitted vacuum
Vacuum-proof
BSP,
flush-mounted
2 bar
10 bar
2 bar
5 bar
10 bar
20 bar
50 bar
100 bar
250 bar
400 bar
600 bar
10 bar
40 bar
10 bar
20 bar
40 bar
80 bar
105 bar
200 bar
400 bar
650 bar
750 bar
15 bar
50 bar
15 bar
25 bar
50 bar
120 bar
210 bar
300 bar
625 bar
1000 bar
1200 bar

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Bsp v s1b serie

Tabla de contenido