Overload Relay with 
Phase Loss Sensitivity
Operating Instructions
Read and understand these instructions before installing, 
operating, or maintaining the equipment.
DANGER
!
Hazardous voltage.
Will cause death or serious injury.
Turn off and lock out all power supplying this device before
working on this device.
CAUTION
Reliable functioning of the equipment is only ensured with 
certified components.
Fig. I
: 3US56: For mounting on contactors 3TS35 / 36,
Individual mounting possible with assembly kit 3US1956.
Mounting
Dimension drawings
(dimensions in mm):
1)
Keep distance to earthed parts.
2)
Where 3TS35/36 contactors are screwed or snapped onto a standard
mounting rail (35 x 7.5 mm rail to DIN EN 50 022) fixed onto a non-insula-
ting surface, insulation should be provided between the relay and the non-
insulating surface so as to obtain the air gap specified in UL 508.
3)
for snap-on fastening on standard sectional rail, DIN EN 50 022.
Dimension for square OFF button (stroke 3 mm).
Dimension for round RESET button (stroke 2.5 mm) dimension minus
2.5 mm.
Permissible installed positions: Fig. III
a Overload relay with contactor
b Overload relay with terminal bracket
Do not subject to sudden shocks or long-term vibrations.
Connection
Permissible cable cross-sections: Fig. V
Equipment circuit diagram: Fig. IV
In the case of several single-phase loads, the three main circuits must be
connected in series.
Commissioning
Instructions: Fig. VI
¿ Set the scale to the rated current of load.
À Reset button (blue)
Push this button before commissioning and after tripping to make relay
ready for operation.
In the as-delivered condition, the auxiliary contact is set to H = Manual
resetting.
To change from H = Manual to A = Automatic, press and turn the button
counter-clockwise from H to A.
Á Test button (red)
When this button is actuated, the NC contact opens and the NO contact
closes, i.e. a test function for NC and NO contacts (simulation of overload
tripping).
In the "Manual" position, the relay is reset when the blue button is
pressed.
In the „Automatic" position, the relay is reset automatically when the red
button is released.
 TRIPPED indication (green)
In the H setting, a green pin protrudes from the front plate to indicate the
TRIPPED condition. In the A setting, this condition is not indicated.
à Terminal for contactor coil, A2.
Tripping characteristics: Fig. VII
The characteristics conform to VDE 0165, VDE 0170 / 0171 for 
machines with type of protection E Ex e.
A5E02261860A-02
Order No.: 3ZX3012-0US56-0AY0
Fig. II
DIN VDE 0660 part 102, IEC 60947-4-1,
Tripping times are shown for a three-phase load from the cold state 
(ambient temperature +20 °C). In the case of hot relays, preloaded with
1 x I
, the tripping times decrease by approx. 25 %.
E
I
: Current setting
E
t
: tripping time in seconds (+ 20 %)
A
¿ Setting range (I = lowest value of current setting I
current setting I
)
E
À Type designation / Order No..
Technical data
Main circuit
Rated insulation voltage
Rated operational current
Permissible ambient air temperature
Degree of protection
Auxiliary circuit
Rated insulation voltage:
400 V
different potential
Rated operational current:
AC-15 / U
V
24
e
AC-15 / I
A
2
e
DC-13 / U
V
24
e
DC-13 / I
A
2
e
Short-circuit protection:
NH, NEOZED or DIAZED fuses
Miniature circuit-breaker
Operating conditions at ambient temperatures > 55 °C
At ambient temperatures > 55 °C, you must
1. Reduce the current loading for the overload relay
2. Upwardly correct the setting current to prevent tripping at motor rated
current.
Correction factors:
Ambient
Perm. Current loading
temperature
referred to end-of-scale value
55 °C
60 °C
65 °C
70 °C
Calculation example:
Motor rated current: 10 A
Ambient temperature: 70 °C
Overload relay fitted: 8 to 12.5 A
1st Step: Determine the permissible current loading:
Max. current loading: 12.5 A x 0.82 = 10.25 A
Loading with motor rated current 10 A at 70 °C ambient temperature is per-
missible.
2nd Step: Calculate the setting current:
Motor rated current: 10 A
Setting current correction: 10 A x 1.1 = 11 A
You must set the overload relay to 11 A.
For further information and accessories, see Catalog.
3US56
Q/320500 SMS 011, GB14048.4
English
, II = highest value of
E
690 V
1.0 ... 45 A
-25 °C .... +55 °C
see nameplate
690 V
same potential
60
125
230
400
500
1.5
1.25
1.15
1.1
1
60
110
220
0.5
0.3
0.2
6 A, Dz 10 A
3 A (C-characteristic)
Setting current
correction
1
1
0.94
1.08
0.88
1.09
0.82
1.1
Last update: 01 April 2011
690
0.8

Publicidad

loading

Resumen de contenidos para Siemens 3US56

  • Página 1 1.0 ... 45 A certified components. Permissible ambient air temperature -25 °C ..+55 °C Fig. I : 3US56: For mounting on contactors 3TS35 / 36, Degree of protection see nameplate Individual mounting possible with assembly kit 3US1956. Auxiliary circuit...
  • Página 2: Conexión

    - 25 °C ..+ 55 °C Grado de protección Ver placa de características Fig. I : 3US56: para montaje en contactores 3TS35 / 36. Montaje individual possible con set de montaje 3US1956. Circuito auxiliar Tensión de aislamiento asignada: Montaje Dibujos acotados Fig.
  • Página 3 Tensão nominal de isolamento 690 V Fig. I : 3US56: para montagem em contatores 3TS35 / 36. Corrente nominal de funcionamento 1,0 ... 45 A Montagem individual possível com kit de instalação 3US1956. Temperatura ambiente do ar admissível - 25 °C ..
  • Página 4: Руководство По Эксплуатации

    гарантируется только при использовании сертифицирован- Дополнительный контур ных компонентов. Номинальное напряжение изоляции: Рис. I: тепловое реле защиты от перегрузки 3US56 для монтажа на кон- такторы 3TS35 / 36. 690 B 400 B При использовании адаптера 3US1956-_ реле может быть установлено...
  • Página 5 技术参数 操作设备时必须确保切断电源。 主回路 690 V 额定绝缘电压 小心 1.0~45 A 额定工作电流 只有使用经过认证的部件才能保证设备的正常运转。 + 55 °C 允许的环境温度 °C 图 I 3US56:与 3TS35 / 36,接触器组合安装。 短路保护 见铭牌 配用附件 3US1956 也可单独安装。 辅助回路 安装 额定绝缘电压 安装尺寸见图 II (单位:mm) 400 V 690 V 注: 不同电位 同电位...
  • Página 6 Technical Assistance: Telephone: +49 (0) 911-895-5900 (8°° - 17°° CET) SIEMENS AG Fax: +49 (0) 911-895-5907 Technical Assistance E-mail: technical-assistance@siemens.com Würzburger Str. 121 Internet: www.siemens.com/industrial-controls/technical-assistance D-90766 Fürth Subject to change without prior notice. Store for use at a later date. Order No.: 3ZX3012-0US56-0AY0 © Siemens AG 2011...