BTL7-S5 _ _ D-M _ _ _ _ -TT 2/3-S32/KA _ _ /FA _ _
Magnetostrictive Linear Position Sensor – Rod Style
Installation (continued)
For horizontal assembly with nominal lengths > 500 mm,
support the rod and tighten it at the end if necessary.
If installed in a hydraulic cylinder, the magnet should not
make contact with the rod. Minimum bore diameter in the
support piston:
Rod diameter
21 mm
Shielding and cable routing
Defined ground!
The BTL and the control cabinet must be at the
same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect the BTL and controller using a shielded cable.
Shielding: Braided copper shield with minimum 85%
coverage.
Connector version: Shield is internally connected to
connector housing.
Cable version: On the BTL side the cable shielding is
connected to the housing.
Ground the cable shielding on the controller side
(connect with the protective earth conductor).
Magnetic fields
The position measuring system is a magnetostrictive
system. Ensure that there is sufficient distance between
the BTL, holding cylinder and strong, external magnetic
fields.
Cable routing
Do not route the cable between the BTL, controller, and
power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least five
times the cable diameter.
Cable length
BTL7-S...
1) Prerequisite: Construction, shielding and routing preclude the effect of
any external noise fields. Required cable cross-section ≥ 0.6 mm
≤ AWG19.
www.balluff.com
Bore diameter
At least 27 mm
1)
max. 500 m
2
and

Electrical connection

Pin
Wire color
1
YE Yellow
2
GY Gray
3
PK Pink
4
RD Red
5
GN Green
6
BU Blue
7
BN Brown
8
WH White
1) Communication line
Pin assignment of S32 (view from above
on BTL), 8-pin M16 circular plug
Startup
DANGER
Uncontrolled system movement
When starting up, if the position measuring system is
part of a closed loop system whose parameters have not
yet been set, the system may perform uncontrolled
movements. This could result in personal injury and
equipment damage.
► Persons must keep away from the system's
hazardous zones.
► Startup must be performed only by trained technical
personnel.
► Observe the safety instructions of the equipment or
system manufacturer.
1. Check connections for tightness and correct polarity.
Replace damaged connections.
2. Turn on the system.
3. Check measured values and adjustable parameters
(especially after replacing the BTL or after repair by the
manufacturer). Recalibrate the BTL, if necessary.
Operating notes
Regularly check function of the BTL and all associated
components.
Take the BTL out of operation whenever there is a
malfunction.
Secure the system against unauthorized use.
BTL7-S5...
+Clk
+Data
–Clk
La
1)
–Data
GND
10...30 V
Lb
1)
english