Magnetostrictive Linear Position Sensor – Profile Style
4
Installation and connection (continued)
4.2

Electrical Connection

The BTL is connected using a plug connection (see
Accessories on page 14).
Pin
Wire color
1
2
OG/WH
Orange/
white
3
OG
Orange
4
5
GN/WH Green/white
6
BU
Blue
7
BN
Brown
8
GN
Green
Unassigned leads that are not used can be connected to the GND on the
1)
controller side but not to the shield.
Reference potential for supply voltage and EMC-GND.
2)
Tab. 4-2:
Pin assignment of S115 connector
Fig. 4-4:
Pin assignment of S112 (view from above on BTL),
8-pin M12 circular plug
8
english
BTL6‑V11V‑... interface
Not used
1)
Tx+
Tx−
Not used
1)
Rx+
GND
2)
20...28 V
Rx−
4.3

Shielding and cable routing

Defined ground!
The BTL and the control cabinet must be at the
same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
Connect BTL and controller using a shielded cable.
Shielding: Braided copper shield with minimum 85%
coverage.
Shield is internally connected to connector housing.
Magnetic fields
The position measuring system is a magnetostrictive
system.
Be sure to provide sufficient distance of the BTL from
strong external magnetic fields.
Cable routing
Do not route the cable between the BTL, controller, and
power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Inductive stray noise from AC harmonics (e.g. from phase
angle controls) are especially critical and the cable shield
offers very little protection against this.
Cable length
The maximum cable length when using CAT5e cables is
100 m.