Programming temperature rea-
dout origin
The RS1 remote probe must be configured
on the DPC thermostat as S2.
To configure the origin of the probe, go to
the main screen that indicates the ambient
temperature and the time.
����
- Press the
key.
- Press keys
simultaneously.
����
- Press the
key. Submenu P2 should
appear on the hour side.
- Press the
key to select the origin of
the probe as S2.
- Press the
key to validate.
- Press the
key to go back to the main
screen.
Programming temperature rea-
dout calibration
Readout of the RS1 remote probe must
be calibrated on the DPC thermostat once
installed.
To configure temperature readout, go to
the main screen that indicates the ambient
temperature and the time.
����
- Press the
key.
- Press keys
simultaneously.
- Submenu P1:S1 should appear on the
hour side.
- Press the
key to select P1:S1.
- Press the
and
calibration, up to a maximum of 3° C posi-
tive and negative.
- Press the
key to validate.
- Press the
key to go back to the main
screen.
15 minutes later, recheck the remote probe
readout with a calibrated thermostat and, if
necessary, adjust probe calibration.
Table of lockouts
Code
91
92
93
94
95
96
97
98
99
All data and dimensions are subject to change without prior notice.
6
Table of temperatures
The following table indicates the ratio
between the temperature, heater and volt-
age.
Temperature °C
keys to modify
NTC value
-5
-4
-3
-2
-1
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
Designation
Selected probe not valid or short circuited probe
Thermostat internal probe not calibrated
No communication between the thermostat
Failure with terminal "AL" connected
Digital probe S5 not detected
Digital probe S6 not detected
Digital probe S7 not detected
Digital probe S8 not detected
Outdoor digital probe not detected
GB
15KOhm ambient probe: DPC-1 and
DPC-1R thermostats, ambient remote probe
(RS-1), duct remote probe (DS-1) and aver-
age probe (AS-1).
57 382
54 657
52 077
49 633
47 317
45 122
43 041
41 068
39 196
37 419
35 733
34 132
32 612
31 167
29 795
28 490
27 250
26 070
24 947
23 880
22 863
21 895
20 974
20 096
19 259
18 462
17 702
16 978
16 287
15 627
14 998
14 398
13 824
13 277
12 754
12 254
11 777
11 321
10 884
10 467
10 068
9 686
9 321
8 971
8 636
8 316
8 009
7 715
7 433
7 163
6 904
6 656
6 418
6 189
5 970
5 760
Voltage
0.445
0.464
0.483
0.503
0.523
0.544
0.566
0.587
0.610
0.633
0.656
0.680
0.704
0.729
0.754
0.779
0.805
0.832
0.858
0.885
0.913
0.941
0.969
0.997
1.025
1.054
1.083
1.112
1.141
1.171
1.200
1.230
1.259
1.289
1.318
1.348
1.378
1.407
1.436
1.466
1.495
1.524
1.553
1.581
1.610
1.638
1.666
1.694
1.721
1.748
1.775
1.801
1.827
1.853
1.878
1.904

Publicidad

Tabla de contenido
loading

Tabla de contenido