PowPak
|
Installation
Programming without a Vive Hub
Dimming Module with 0 –10 V-
Part of the Vive Family
Start Here
Associate Wireless Transmitters to
1
PowPak Dimming Module with 0 –10 V-
Before beginning this step, make sure that there are no other
PowPak modules being set up within the same building. It is
possible that wireless transmitters from other systems can be
incorrectly associated to this module.
A On PowPak Dimming Module with
0 –10 V-, hold Toggle button " u "
for 6 seconds until lights flash.
The Load Status LED will begin
flashing twice per second.
B Hold the indicated button on each transmitter for 6 seconds.
Lights will flash to show that wireless transmitters have been
associated.
Link
Cal.
Test
C On PowPak Dimming Module with 0 –10 V-, hold Toggle
button " u " for 6 seconds to save association. Lights will
flash and LED will quickly blink for 2 seconds.
D Permanently install wireless transmitters (consult individual
component installation guides for information).
Reset Factory Defaults
Note: In some instances, it may be necessary to reset the PowPak
Dimming Module with 0 –10 V- and connected devices back to
factory default settings. Before beginning, make sure that all devices
are connected and powered.
A Rapidly tap the Toggle button " u " on the PowPak Dimming Module
3 times and hold on the fourth time until the LED begins to flash at
a rate of approximately 2 blinks every 1 second; then release the
Toggle button " u " .
B Within 3 seconds of the start of flashing of the LED on the PowPak,
rapidly tap the Toggle button " u " on the PowPak Dimming Module
3 times again. Make sure to release the Toggle button " u " after the
third press.
C The LED will flash at a rate of 2 blink every 3 seconds and the
connected load will cycle 3 times to indicate the unit has been reset
to factory defaults.
Note: Any associations or programming previously set up with the
PowPak will be erased and will need to be re-programmed.
Lutron, Pico, PowPak, Radio Powr Savr, and Vive are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the US and/or other countries. Safari is a trademark of Apple Inc., registered in the U.S. and other countries. All other product names, logos, and brands are property of their respective owners. ©2013 – 2020 Lutron Electronics Co., Inc.
Calibrate the Radio Powr Savr Daylight Sensor
2
Daylight Sensor will control all wired fixtures equally.
A Press and release the "Cal." button on the Daylight Sensor.
B Set lights in room to desired light level.
C Press and hold the "Cal." button for 6 seconds.
D Exit room for 5 minutes to complete calibration.
Note: When calibration has completed, all lights will flash and begin to respond to daylight.
Multiple Daylight Rows (Optional)
For every row of daylighting a separate PowPak Dimming Module with 0 –10 V- must be
used. For detailed setup refer to the tuning section of the Radio Powr Savr Daylight Sensor
installation guide.
• Select the PowPak Dimming Module with 0 –10 V- that you want to adjust by pressing the
toggle button.
Set a Favorite Light Level
(Optional)
3
For Pico remote controls with a Favorite button.
A Adjust lights to desired level:
Use the Raise button " " or Lower button " " on the Pico
remote control.
B Save favorite level:
Press and hold the Favorite button for 6 seconds. The load will
flash 3 times to confirm that the Favorite level is saved.
Set Low-End Trim and High-End Trim
4
For best results, minimize the amount of sunlight entering the room before
performing the following procedures.
Notes
Depending on the fixture manufacturer or load, low-end trim and high-end trim
may need to be adjusted.
• Trim low-end to ensure a stable light level because some loads will flicker or drop out if
trimmed too low.
• Be sure that you can turn on the lights to the low-end trim level without any
abnormal operation.
• The factory default high-end trim is suitable for most applications but can be
adjusted as desired.
Low-End Trim
A Enter low-end trim adjustment mode:
Press and hold the Lower button " " on the fixture control for 12 seconds.
The lights will flash and the load status LED will begin flashing.
B Adjust the low-end trim:
Use the Raise button "▲" and Lower button " " on the fixture control to adjust and set the
lights to the desired low-end (1 to 45%).
C Save the low-end trim:
Press and hold the Toggle button " u " for 6 seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
High-End Trim
A Enter high-end trim adjustment mode:
Press and hold the Raise button "▲" on the fixture control for 12 seconds.
The lights will flash and the load status LED will flash.
B Adjust the high-end trim:
Use the Raise button "▲" and Lower button " " on the fixture control to adjust and set the
lights to the desired high-end (55 to 100%).
C Save the high-end trim:
Press and hold the Toggle button " u " for 6 seconds to save setting.
The load status LED will begin flashing and then turn solid to indicate new level has been saved.
Set Minimum Light Level
5
Certain applications (e.g., hallways), may require that the lights never turn off. For these areas, activate Minimum Light Level
mode.
Link
Cal.
Test
A Enter minimum light level adjustment mode:
Press and hold Toggle button " u " and Lower button " " for 12 seconds. Lights will flash high-low-high and LED will begin
flashing.
If lights stop flashing and go to high-end, the minimum light level is set to OFF (default).
If lights stop flashing and go to low-end, the minimum light level is ON and set to low-end.
B Change the minimum light level:
Press Raise button "▲" to set minimum light level to low-end.
Press Lower button " " to set minimum light level to OFF.
C Save the minimum light level:
Press and hold Toggle button " u " for 6 seconds. LED will quickly flash to indicate that new level has been saved.
Set Occupancy Light Levels
6
Note: Unoccupied light level is always the minimum light level and cannot be adjusted.
Raise
Lower
A Set desired occupancy light levels:
Use the Raise/Lower buttons "▲ / " on the PowPak Dimming Module with 0 –10 V- or the Raise/Lower buttons " /
all associated Pico Remote Controls to dim the lights to the desired level. Note: Setting lights to OFF during this step will
make that control module unaffected by occupancy (will function as vacancy only).
B Save occupancy light levels:
Press and hold Test button for 6 seconds on any associated Radio Powr Savr Occupancy Sensor without a Lights On
button. Release when the sensor lens starts to flash.
Favorite
Or, press and hold Lights On button for 6 seconds on any associated Radio Powr Savr Occupancy Sensor. Release when
the sensor lens starts to flash.
(Optional)
Troubleshooting
Ballasts cannot be controlled
locally from PowPak Dimming
Module with 0 –10 V-.
Lights do not dim as expected.
Lights do not respond to Wireless
Transmitter(s).
Lights are unstable at low-end or
flash/flicker at turn-on or turn-off.
Wireless Transmitter(s) cannot be
associated to PowPak Dimming
Module with 0 –10 V-.
PowPak is in emergency mode
(RMJS-8T-DV-B-EM only).
PowPak will not go into
emergency mode
(RMJS-8T-DV-B-EM only).
Customer Assistance:
U.S.A., Canada, and the Caribbean: 1.844.LUTRON1
Mexico: +1.888.235.2910
Brazil: +55.1.3257.6745
Limited Warranty: www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
For FCC/IC information: Please visit: www.lutron.com/fcc-ic
Customer Assistance www.lutron.com/support
(Optional)
(Optional)
• Ensure that the breaker(s) to the PowPak Dimming Module with 0 –10 V- are energized.
• Ensure that the PowPak Dimming Module with 0 –10 V- switched hot lead is wired to the lighting fixture(s).
• Ensure that the PowPak Dimming Module with 0 –10 V- control lines are wired to the lighting fixture(s).
Reset to factory defaults.
• Ensure that 0 –10 V- control lines are wired properly.
• Ensure that fixture does not require an inverted signal (10 – 0 V- control).
• Ensure that the breaker(s) to the PowPak Dimming Module with 0 –10 V- and ballasts are energized.
• Ensure that Wireless Transmitters are associated to the PowPak Dimming Module with 0 –10 V-.
Reset to factory defaults.
• Adjust low-end trim.
• The maximum number of Wireless Transmitters have been associated to the PowPak Dimming Module with
0 –10 V-. To remove a previously set up Wireless Transmitter, tap a Wireless Transmitter button three times; on
the third tap hold for three seconds and then tap three more times.
• In systems with a Vive hub: Contact Lutron Customer Assistance for further details.
• In systems without a Vive hub: Wait 90 minutes for the PowPak to return to normal operation.
Contact Lutron Customer Assistance for further details.
Central / S. America: +1.610.282.6701
Other Countries: +1.610.282.3800
www.lutron.com/support
" on
www.lutron.com/support

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Powpak urmjs-8t-dv-bPowpak rmjs-8tn-dv-b

Tabla de contenido