1SFC101002M5501
M12
45 N.m - 398 lb.in
A1
A2
M 3,5
1 Nm (9Ib.in)
AF 1350(T), 1650(T), 2050(T)
!
According to UL 60947- 4 - 1
AF1350, AF1650: Use terminal kit K7TK, wire 4/0 AWG - 500 kcmil, Cu 75 °C only, 375 in - lb.
AF2050: At 2100A 600V AC, use copper bars each of minimum four busbars per terminal
2
1/2
At 1900A 600V DC, use copper bars each of minimum two busbars per terminal 4 inch
(width) by 1/4 inch (thickness). Three poles connected in series.
AF1350, AF1650 and AF2050 Enclosure with three latches and with min.dimension
79 by 32 by 20 inches should be used.
All contactors: * Designed for max 40° C surround temperature.
ø 5,0
Pz 2
Torx T25
M6
Torx T25
4 Nm
inch(width) by 1/4 inch (thickness).
Flexible
Solid / Stranded
2 x 0,75 ... 2,5 mm²
2 x 1 ... 2,5 mm²
CU 75 C
Lugs
I > 3,5 mm
L < 8 mm
M8
22 Nm
4/7
100 mm