Descargar Imprimir esta página

Atlantic Varfree Manual De Instalación página 25

Kit de intercambiabilidad

Publicidad

EN
Electrical connections and confi gurations:
!
01.02.2017
CAUTION:
If the boiler replaced has an OCI 420:
Put the OCI 345 in place (refer to the manual supplied with the module).
Set parameters 6600, 6601, 6640 et 6604 (LPB network menu on the NAVISTEM
B3000) as follows:
Set parameter 6600 with the value of parameter H605 (read on the boiler replaced).
Set parameter 6601 with the value of parameter H606 (read on the boiler replaced).
Set parameter 6640 according to the values of parameters H604.b0 and H604.b1
(read on the boiler replaced):
Old boiler
H604.b0
0
1
0
Set parameter 6604 according to the value of parameter H604.b2 (read on the boiler
replaced):
Old boiler
If the boiler replaced had an AGU 2.511:
Connect the 0-10V control cable to H1-GND on the NAVISTEM B3000.
Confi gure the H1 input on the NAVISTEM B3000:
Parameter
No.
5950
H1 input function
5953
H1 voltage 1 value
5954
H1 function value
5955
H1 voltage 2 value
5956
H1 voltage 2 value
KIT VARFREE - Installation, Instalación, Installatie
The power must be switched off when each accessory
is connected.
Close the panel's protective cover before powering
up for confi guration.
H604.b1
0
Independent
0
Slave without adjustment
1
Master
H604.b2
0
Stop
1
Automatic
Title
10C consum1 circ. request
0.0
0
10.0
1000
(for an equivalence 10 V = 100 °C)
New boiler
6640
New boiler
6640
Value to be programmed
25 / 36

Publicidad

loading