Quick Start Guide
®
X
– Series Gas Monitor
3
ULTIMA
This quick start guide does not replace the operating manual. It is imperative that the
operating manual file on the CD be read and observed when using the apparatus. In
particular, the safety instructions, as well as the information for the use and operation of
the apparatus, must be carefully read and observed.
The operating manual can also be provided as a hard copy upon request.
1
(1)
Unscrew the enclosure lid and remove the electronics module.
(2)
Mount the enclosure in the desired location and run suitable wiring to
the enclosure.
(3)
Install the sensor module in the applicable threaded entry or connect
remote sensor - catalytic and electrochemical sensors must point
downwards, XIR sensor must be horizontal.
(4)
Connect 24 VDC power to connector J8 DC.
(5)
Connect the signal ground wire to J8 GND.
(6)
Connect the sensor modules to the appropriate sensor
connector1, 2 or 3.
(7)
Connect optional relays and/or external reset (acknowledge)
push-button to J10.
(8)
If using Modbus communication please refer to the operating
manual for wiring details
(9)
Replace the electronics module and the lid on the enclosure.
(10) Apply power and observe the LCD as all the segments light, the
software version displays and a 30 second (self check) countdown
occurs.
(11) After the 30 second countdown, observe that the gas type and gas
concentration alternately display (for three wire units with LEDs,
green LED is ON and red LED is OFF).
(12) Perform a gas calibration to ensure proper operation.
GB
3
2
4
5
6
7
1 Enclosure with viewing window
2 Sensor electronics with LEDs and display
3 Display
4 Flameproof enclosure
5 Sensor housing
6 Sensor module
7 SensorGard
Order No.: 10083026/02