Battery Block Monitoring; Mounting/Connecting The Battery Block Sensors; Retrofitting Of Bdm Modules - Eaton BBS 12V M6 Manual De Instrucciones

Tabla de contenido

Publicidad

Battery block monitoring

Battery block monitoring
Mounting/connecting the
battery block sensors
After installing the battery terminal jumpers, con-
nect the battery block sensors. Pay attention to cor-
rect polarity. Connect the black minus cable with bat-
tery minus and the red plus cable with battery plus.
As the battery block temperature measurement is carried
out via the negative lead of the battery block sensor, the
battery block sensor housing does not need to have a heat
conducting connection with the battery block housing.

Retrofitting of BDM modules

For the subsequent installation of the BDM modules in
the DualGuard-S devices an adapter is required which is
clicked into the DIN rail. The DIN rail adapter supplies the
BDM module with 24V voltage and establishes the bus
connection to the ACU module.
1) Remove the ACU module from the DIN rail.
2-3) Click the DIN rail adapter into the DIN rail.
4) Snap on the ACU module.
5) Snap on BDM module or CAN bus adapter.
If the ACU module and the BDM module are mounted
separately, the CAN bus adapter must be installed next to
the ACU module for the bus connection.
The BDM module is then connected to the CAN bus
adapter via a 4-wire shielded bus cable.
6
Mounting- and operating instructions Battery block monitoring 40071860356 (D) March 2021 www.ceag.de
NOTE!
The CAN bus must be termina-
ted at the beginning and at the
end with a 120 Ohm resistor.
SAFETY NOTICE WARNING!
RISK OF INJURY!
Improper installation and installation can lead to serious
personal injury and/or damage to property. This work may
therefore only be carried out by authorized, instructed
personnel familiar with the operation of the device and in
compliance with all safety regulations.
• Ensure sufficient freedom of movement.
• Ensure order and cleanliness at the workplace. Loose or
loose components and tools are sources of accidents!
IMPORTANT NOTE
Please observe the torques specified by the battery manu-
facturer when connecting.
1)
2)
3)
4)
5)

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Bdm4007136178040071362190Dualguard-s

Tabla de contenido