Battery block monitoring – General description
Battery block monitoring –
General description
The BDM Battery Data Module automatically records volta-
ge and temperature values during initial commissioning and
recurring tests. In addition, the battery block monitoring sys-
tem enables automation of the annual operating life test, as
manual cyclic measurement of the individual battery block
voltage values is no longer required. A potential-free chan-
geover contact reports the operating status to a higher-level
building management system if required. Warning and
alarm display in the event of deviations in the high charge
voltage, charge retention voltage, discharge voltage and
battery block temperatures of each individual battery block
are displayed and logged on the TFT touch display and by
the maximum 72 battery block sensors (BBS). The wireless
data transmission of the sensor data to the BDM module
simplifies the installation of the BBS battery block sen-
sors as no additional data line is required. The minus pole
temperature measurement via the sensor cable ensures
that no direct, temperature conductive connection of the
BBS battery block sensor to the battery housing is neces-
sary. Easily recognisable status displays through translu-
minescent, robust BBS sensor housing with integrated,
Dimensions (LxHxD)
Material
Weight
Mounting
Ingress protection
Protection class
Ambient temperature
LED´s
Service Pin
Contact
Order details
Type
BDM Modul
BBS Sensor 12V/M5
BBS Sensor 12V/M6
BBS Sensor 6V/M8
4
Mounting- and operating instructions Battery block monitoring 40071860356 (D) March 2021 www.ceag.de
BDM-Modul
90 x 72 x 60 mm
Polycarbonate UL94V-0
0.06 kg
DIN rail
IP20
II
-5°C....+35°C
BDM Modul
The red LED flashes at 1 Hz and the green LED
is off: The BDM module is not yet registered.
The green LED is on continuously: The BDM
module is registered.
The red LED is on continuously: There is a fault.
The green LED flashes: Sensors are being
searched for and connected to the BDM mo-
dule.
To register the BDM module
with the ACU module
Potential-free N/O contact 24 Vrms / 0.5A for
signalling faults.
Scope of delivery
Battery Data Bus Module for top hat rail mounting
Battery Block Sensore for 12V Battery Blocks with M5 Connector. 18Ah
Battery block sensor for 12V battery blocks with M6 connector.
23,3Ah, 32Ah, 39,8Ah, 50,4Ah, 53,7Ah, 66,2Ah, 85,7Ah, 89,4Ah
Battery block sensor for 12V battery blocks with M8 connector. 118Ah
mechanically protected LED provide clarity at first glance.
An automatic configuration routine via soft addressing and
the menu navigation of the TFT touch display via user icons
makes it very easy to register the sensors with the system.
BBS Sensor
90 x 53 x 17 mm
Polycarbonate UL94V-0
0.05 kg
Free wiring. No temperature conductive connection
with the battery block surface necessary
IP20
II
-5°C....+35°C
BBS Modul
Flashing with 10 Hz for 1 s when measuring
data is transmitted, otherwise OFF
Short ON during network formation (module
found)
Flashing 1 Hz: battery error
Flashing 0.5 Hz: Communication error with
BDM
Order no.
40071361780
40071362030
40071362190
40071362202

Publicidad