IN CASE OF FIRE: Automatic System Operation
1) Detector(s) registers alarm condition in the hazard area and
initiates the time delay on the control module.
2) "PUSH To Activate / Alarm When Lit" LED and sounder:
a. Pulse 2 x 1 sec. until last 5 sec. of Time Delay; then
pulse 4 x 1 sec. during final 5 sec. To restart time delay
press and release DELAY/RESET/SILENCE (Grey)
button (see below for more information).
b. After time delay, "PUSH To Activate / Alarm When Lit"
LED and sounder are steady-on for 10 sec. during
initiation (release) of fire suppression system (if included,
pressure switch activates auxiliary functions).
3) As soon as time delay begins: Safely stop equipment, set
brake, shut off engine, and exit. Standby with supplemental
firefighting equipment.
DELAY/RESET/SILENCE (Grey) Button
1) Restart Time Delay: Press and release to restart the time
delay cycle during alarm condition.
a. Must be initiated before release circuit activates.
b. Note: Press and hold will not extend time delay period.
2) Silence sounder (post discharge or fault notification)
for two hours: Press and release to silence sounder; LED
fault indication will continue until fault is cleared. Any new
fault or detection event will reactivate sounder.
3) Reset function is for Authorized ANSUL Distributor service
technician.
PUSH GREY BUTTON TO
RESTART TIME DELAY
PAGE 3
009180