Operation

Checking the DC voltage

When placing the probes on an AC voltage within the rated voltage range, one of the lower (12 V +~-) LED's and the LED arranged
above it illuminate according to the voltage applied. The lower LED's indicate the polarity at the test probes L2! ( + or - )
If the threshold value of approx. 35 V is exceeded, the ELV LED also illuminates and lucid vibration can be felt. This indicates
a hazardous voltage is present!
The ELV LED must not be used for measurement.

Checking the AC voltage

When placing the probes on an AC voltage within the rated voltage range, both of the lower (12 V +~-) LED's and the LED's ar-
ranged above them illuminate according to the voltage applied. The simultaneous illumination of the lower LED's indicates AC volt-
age (~).
If the threshold value of approx. 35 V is exceeded, the ELV LED also illuminates and lucid vibration can be felt. This indicates a
general hazardous voltage!
The ELV LED must not be used for measurement.

Phase test

Protective clothing and insulation locations can influence the function!
With the test probe "L2", contact the large hand parts of a conductor. If a phase (Pol >100 V AC), min. 100 V~ is applied, the
"<L" LED illuminates! Momentarily illumination of the 12 V LEDs has no significance here.
For determining the phase conductor, the perceptibility of the indication can be impaired, e.g. by insulating fix-
tures to protect against direct contact, in adverse positions, for example on wooden ladders or insulating floor
coverings, of a voltage not earthed or also in adverse lighting conditions.
For safety, check for two-pole deenergization.
The phase can also be determined by checking the external conductor against the protective earth. The voltage applied should be
indicated at the phase conductor.
During this test, make sure that an additional current flows across the protective conductor. This is added to that
already existing and could trigger the circuit breaker (FI))!
Phase sequence testing (> 200 V AC)
Protective clothing and insulation locations can influence the function.
Fully encompass the handles L1 and L2 (refer to the figure on Page 15) below the mechanical mark.
Place the probes L1 and L2 on two external conductors (phases) and check to see whether the external conductor voltage of,
e.g. 400 V is applied.
A clockwise sequence (phase at L1 before phase at L2) is present if the "R" LED illuminates.
An anticlockwise sequence (phase at L2 before phase at L1) is present if the "L" LED illuminates.
Determination of the phase sequence must always be carried out with a check for transposed probes. Thereby, the phase se-
quence must change.
Please note:
The phase sequence test is possible in earthed AC voltage mains supply from 200 V, 50/60 Hz (phase to phase). The "third" phase
(L3) is simulated with the aid of a sensor in the instrument, by using the hand parts.

One-hand test (e.g. Schuko socket)

Locking both hand parts is possible by the distance piece located on the test line in the lower section on the L1 hand parts. The dis-
tance of the test probes can be adjusted by simply rotating. (Schuko / CEE).

Test location lighting

The lighting at the test location is switched on and off by momentarily activating the L.H button.
Carefully insert these because, due to the additional load, the batteries become discharged prematurely.

Continuity test

(To switch on, place the test probes on one another)
Place the test probes on the line to test, fuse or similar. For a resistance of 0 - 200 k, the green "Rx/" LED illuminates and an
acoustic signal sounds.