Indoor unit(s)
Model(s):
Outdoor side heat exchanger of heat pump: Air
Indoor side heat exchanger of heat pump: Air
Indication if the heater is equipped with a supplementary heater: no
If applicable: driver of compressor: electric motor
Parameters shall be declared for the average heating season, parameters for the warmer and colder heating seasons are optional.
Item
Symbol
Rated heatling
Prated,h
capacity
Declared heating capacity for part load at indoor temperature
20 °C
and outdoor temperature Tj
Item
symbol
Tj = -7℃
Pdh
Tj = 2℃
Pdh
Tj = 7℃
Pdh
Tj = 12℃
Pdh
Tbiv = bivalent
Pdh
temperature
TOL = operating limit
Pdh
For air-to-water heat
pumps: Tj = – 15 °C
Pdh
(if TOL < – 20 °C)
Bivalent
Tbiv
temperature
Degradation
co-efficient heat
Cdh
pumps (**)
Power consumption in modes other than 'active mode'
Off mode
Poff
Thermostat-off
PTO
mode
Crankcase heater
PCK
mode
Capacity control
Sound power
level,indoor/outdoor
LWA
measured
Emissions of
nitrogen oxides (if
NOx (**)
applicable)
GWP of the
refrigerant
SALVADOR ESCODA SA
NÁPOLES 249 P1
Contact details
08013 BARCELONA (SPAIN)
+34 93 446 27 80
Information requirements for heat pumps
Outdoor unit
Value
Unit
11,0
kW
value
unit
9,770
kW
6,250
kW
3,997
kW
2,312
kW
9,770
kW
9,670
kW
x,x
kW
-7
°C
x,x
—
0,012
kW
0,020
kW
0,000
kW
Other items
variable
65/73
dB
mg/kWh
x
fuel
input GCV
kg CO2 eq
675
(100 years)
MUCSR-48-H11T-I
MUER-48-H11T-E
Item
Symbol
Seasonal space heating
energy efficiency
Declared coefficient of performance or gas utilisation
efficiency/auxiliary
energy factor for part load at given outdoor temperatures Tj
Item
symbol
Tj = -7℃
COPd
Tj = 2℃
COPd
Tj = 7℃
COPd
Tj = 12℃
COPd
Tbiv = bivalent
COPd
temperature
TOL = operating limit
COPd
For air-to-water heat
pumps: Tj = – 15 °C
COPd
(if TOL < – 20 °C)
For water-to-air heat
pumps: Operation
limit temperature
Supplementary heater
Back-up heating
capacity (*)
Type of energy input
Standby mode
For air-to-air heat pumps:
air flow
rate, outdoor
measured
For water/brine-to-air
heat pumps: Rated
brine or water flow
rate, outdoor side heat
exchanger
Value
Unit
ηs,h
157,0
%
value
unit
270,0
%
410,0
%
478,7
%
545,3
%
270,0
%
236,5
%
x,x
%
Tol
-10
°C
elbu
1,374
kW
Psb
0,012
kW
—
7500
m3/h
—
x
m3/h