GATE DELAY DURING OPENING
In order to avoid any collision of the gate during the opening
phase, the time of delay should be introduced r.AP, which is
adjustable from 0 to 120 seconds (±0,5) .In such a case the
opening time of gate 2 is delayed in comparison to the gate 1.
GATE DELAY DURING CLOSING
In order to avoid the colliding of gate's during the closing the time
of delay should de introduced r.Ch, which is adjustable from 0 to
120 seconds (±0,5).In such a case the closing time of gate1 is
delayed in comparison to the gate2.
LOCK TIME
When the gate starts the opening phase, the control unit must
excite the electro lock in order to hook it out and enable the
opening of the gate. The time t.SEr determines the duration of
excitation, and is adjustable from 0 to 120 seconds (±0,5).
LOCK ADVANCE TIME
This menu permits to anticipate the excitation of the lock on a set
time from 0 to t.SEr (with a scanning of ±0,5). During the advance
locking time the gate does not move so to always guarantee the
unhooking of the electrical lock.
BACKLASH TIME
To avoid that the gate starts the opening phase before the
electrical locks is unhooked, it is possible to introduce a time of
inversion adjustable from 0 to 120 seconds (± 0,5). In this way
during the opening phase, the gate inverts the motion through the
set time permitting the unhooking of the electrical lock.
PRE-FLASHING TIME
This menu permits the introduction of a pre-flashing that occurs
before any movement of the gate either in opening or in closing
phase: the time of pre-flashing can be adjusted from 0 to 120
seconds (± 0,5).
SLOWING DOWN TIME
This menu permits the activation of the gate slowing down
function for a time to be set between 0 and 120 s(± 1,5 s). To
set the slowing down function proceed as follows: leave a slowing
down time at 0 and make sure that the gate opens and closes
correctly. After that, set the slowing down time (for ex. 5 or 6 s).
20