Honeywell VRN2BBSA0000 Instrucciones Para La Instalación página 6

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

VRN DYNAMIC PRESSURE-REGULATING CONTROL VALVES AND ACTUATORS
1
24 VAC
2
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
+
FEEDBACK
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING.
1
24 VAC
2
4 TO 20 mA
PROPORTIONING
CONTROLLER
+
FEEDBACK
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING.
Fig. 18. MS7505 with Proportioning Controllers
(Modulating mode setting).
1
SPST
1
LINE VOLTAGE POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 19. MS4105 line voltage (120V) two-position control.
38-00005EFS—02
ACTUATOR
1
V
2
3
OR +
OR N/A
4
5
FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
M34976
ACTUATOR
1
V
2
3
OR +
490 TO 510
OR N/A
4
OHMS,
1/2 W
5
FEEDBACK
MINIMUM
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
M34977
1
V
2
ACTUATOR
M29122
S3
Fig. 20. Wiring for model with aux./end switches.
1
1
24 VAC
0/2 TO 10 VDC
PROPORTIONING
CONTROLLER
HOT
COM
+
1
24 VAC
1
LINE VOLTAGE POWER SUPPLY.
PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
2
24 VDC SUPPLY ACCEPTABLE.
3
SET SWITCH TO MODULATING.
Fig. 21. MS7505 with Proportioning controllers operating
multiple actuators (Modulating mode setting).
NOTE: All identified parts except for the valve body and
aluminum valve stem coupler are included in
Replacement Kit (part no. 5112-11).
OPERATION AND CHECKOUT
Once both the mechanical and electrical installations are
complete:
1. Cycle the actuator to verify that the direction of rotation
suits the control sequence.
2. If the rotation direction is incorrect:
a. For 2-position spring return actuators: Remove, flip
over, and replace actuator on the bracket.
b. For floating control actuators: Reverse two control
signal wires (CW/CCW), or change position of
selector switch.
c. For analog control actuators either:
(3) Change setting of reverse/direct-acting switch, or
(4) Remount actuator on the bracket.
6
S2
S1
M35813
24 VAC
ACTUATOR
2
1
V
2
3
OR +
OR N/A
4
FEEDBACK
5
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
ACTUATOR
1
V
2
2
3
OR +
OR N/A
4
5
FEEDBACK
2-10 VDC
10-2 VDC
0-10 VDC
3
10-0 VDC
Fltg, fwd
Fltg, rev
M34978