Assembly and operating instructions Type 7E.36
65 A-active-energy meter, three-phase, Fig. 1 (2-tariff meter is illustrated)
Description
The 7E.36 is a space-saving, modern, electronic rotary
current meter, of accuracy class 1 (according to EN
62053-21), class°B respectively (according to EN
50470-1). The tamper-proof energy meter is fitted with
a high-quality counting mechanism and can be mounted
on a 35°mm rail regardless of location. The counting
mechanism is fitted with a reverse lock and can be read
at any time even without power supply. External tariff
switching is possible with the double tariff meter.
Technical data
Connection
Fig. 2 (on the 1-tariff meter
diagram
connections E1°–°E2 are missing
for tariff-switching device
R°T1,°T2)
Dimensions
Fig. 3 (on the 1-tariff meter the
right-hand counter is missing)
Characteristics
3-phase, direct connection meter
Class 1 according to
EN 62053-21, Class B according
to EN 50470-1
PTB approval (Germany) and MID
approval (EU and Switzerland)
SO+/SO- output with 1,000
Imp/kWh
Nominal currnt strength In = 10 A
Maximum current strength
I
max
Starting current Ist = 40 mA
Assembly
On 35mm rail (EN 60715TH35)
Counting mech.
0...999.999,9
capacity
Display
Mechanical, 4 mm figures,
decimal point red
Nominal voltage
3 x 230 VAC; 50 Hz; P< 0,4 W
per phase
LED function
flashing (red)
Normal operation 2,000
impulses/kWh (impulse pause:
100 ms):
in kW = Number of impulses
per min x 0.6
4 319 5047 0b
06.2009
= 65 A
No consumption, no
impulses
Low consumption
High consumption
FINDER SpA
Via Drubiaglio, 14
10040 Almese (TO) - ITALY
Notes before connecting
1. Do not connect L1, L2 to L3 to N.
2. In order to avoid moisture in the meter due to
condensate build-up, acclimatise the meter at room
temperature for about half an hour before connecting.
Attention!
These devices must only be installed by a professional
electrician, otherwise there is the risk of fire or the risk
of an electric shock.
Assembly note
The rotary current meter can be mounted onto bearing
rail (EN°60°715°TH35). It may only be installed and
used in installation cupboards with protection type IP 51
(protected against penetrating dust and dripping water).
EC declaration of conformity
Finder SpA declares at its own responsibility:
The following energy meters are in compliance:
7E.36.8.400.0000
7E.36.8.400.0010
7E.36.8.400.0002
7E.36.8.400.0012
The following energy meters are approved for energy
billing:
7E.36.8.400.0010
7E.36.8.400.0012
Additionally they meet the following standards or norma-
tive documents:
EN 50470 parts 1 and 3 (electronic meters)
Directive 2004/22/EC (MID) of the European Parlia-
ment and Council on measuring devices
Appendix I, basic requirements
Appendix MI-003, electricity meters for kilowatt
hours
For year of issue of declaration of conformity according to
Directive 2004/22/EC see printed text on the device.
Example: Declaration of conformity for 2007
Error LED (Phase missing or connection inverted)
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
3 s
Subject to change without notice
English
(1 tariffs)
(1 tariffs)
(2 tariffs)
(2 tariffs)
(1 tariffs)
(2 tariffs)
L1 not connected
L2 not connected
L3 not connected
L1 and L2 swapped
L1 and L3 swapped
L1, L2 + L3 swapped
/ not connected