Selecting The Installation Site; Indoor Unit - Panasonic T2 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 52

2. SELECTING THE INSTALLATION SITE

2-1. Indoor Unit

AVOID:
● areas where leakage of flammable gas may be expected.
● places where large amounts of oil mist exist.
● direct sunlight.
● locations near heat sources which may affect the
performance of the unit.
● locations where external air may enter the room directly.
This may cause "condensation" on the air discharge ports,
causing them to spray or drip water.
● locations where the remote controller will be splashed with
water or affected by dampness or humidity.
● installing the remote controller behind curtains or furniture.
● locations where high-frequency emissions are generated.
DO:
● select an appropriate position from which every corner of the
room can be uniformly cooled.
● select a location where the ceiling is strong enough to
support the weight of the unit.
● select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
● allow room for operation and maintenance as well as
unrestricted air flow around the unit.
● the limitation of the tubing length between the indoor and
the outdoor units should be referred to the Installation
Instructions of the outdoor unit.
● allow room for mounting the remote controller about 1 m off
the floor, in an area that is not in direct sunlight or in the flow
of cool air from the indoor unit.
min. 25 cm
N OT E
The rear of the indoor unit can be installed flush against
the wall.
min. 50 cm
8
Ceiling
Ceiling
min. 25 cm
Front view
Air
discharge
Air intake
Side view
Max. 25 cm
Obstacle
Wall

Publicidad

Tabla de contenido
loading

Tabla de contenido