Configuringa PROFIBUS-DP-System
Parameter selection
When an existing file has been opened or a new file created, all available parameters are
shown in the parameter window.
Fig. 10: Parameter selection
1
List with available parameters
2
Device name for hardware catalog If different GSD files
are required for de- vices of the same type, this
standard name has to be altered in a way that allows
unambiguous assignment of the PROFIBUS master in
the hardware configuration.
Parameter addition or deletion
Using the arrow keys
output window (and back).
The 'Interface status' parameter automatically appears in the input window
and cannot be deleted.
Configuration data (user level)
The device's user level parameters are kept in the Configuration folder. These parameters
may not be written cyclically by the PLC without end, because the corresponding memory
modules of the multichannel measuring instrument have been designed for a limited
number of write cycles (approx. 1 000 000).
4.4

Connection example

4.4.1

Type 202580

1.
Connect the device to the PLC.
2.
Using the device keys or the setup program, set the device address.
417102396 Rev. 1-10.2019
and
, parameters can be moved from the input window to the
28