4.
WORKING
WARNING
!
QUALIFIED PERSONNEL WITH THE RIGHT INSTRUMENTS MUST HANDLE THE BURNER'S START-UP.
4.1
COMBUSTION ADJUSTMENT
In conformity with Efficiency Directive 92/42/EEC the application of the burner on the boiler, adjustment and
testing must be carried out observing the instruction manual of the boiler, including verification of the CO and
CO
concentration in the flue gases, their temperatures and the average temperature of the water in the boiler.
2
To suit the required appliance output, choose the proper nozzle and adjust the pump pressure, the air damper
opening in accordance with the following schedule:
Nozzle
GPH
0.40
0.50
0.60
0.60
0.65
0.75
0.75
0.85
0.85
0.85
1.00
1.10
4.2
RECOMMENDED NOZZLES
Delavan 80° W with filter DROPSTOP type 60030.
4.3
ELECTRODES ADJUSTMENT
ATTENTION
MEASURES MUST BE RESPECTED AND ALSO THE UPWARDS POSITION.
Lean insulators (1) to disc (2), (see fig. 11 - 12).
To have access to the electrodes carry out operation as described in chapter 4.4 – "MAINTENANCE POSITION".
371T1 - 372T1 - 373T1
0
5 + 0.5 mm
2
1
3
D5756
3399
Pump pressure
Angle
bar
80°
12
80°
12
80°
12 / 14
80°
12
80°
12
80°
12
80°
11
80°
12
80°
14
80°
12
80°
12
80°
14
Fig. 11
6 mm
Burner output
±
kg/h
4%
1.35
1.7
2.0 / 2.2
2.0
2.3
2.9
2.6
3.0
3.3
3.0
3.8
4.6
387T1
0
6.5 + 0.5 mm
2
1
D5757
7
GB
4
Air damper adjustment
Set-point
0.25
1.1
2.0
1.1
2.0
2.5
2.2
2.9
4.0
2.2
4.2
6.0
Fig. 12
3
8 mm