The enclosure of the device provides a degree of protection of IP00.
Do not use batteries other than the original batteries supplied by the manufacturer to avoid conflicts with agency approvals.
The maximum surrounding air temperature is +50°C (+122°F). The operational temperature is the same as the ambient or
surrounding air temperature and is defined 2cm below the device. Charging is allowed up to +40°C.
Frequently charging below +5°C reduces the lifetime of the battery.
The device is designed to operate in areas between 5% and 95% relative humidity.
Shorten the length of the (+) and (-) wires as needed between the battery module and the DC-UPS. If separate wires are
used, do not use wires smaller than 4mm
on this connection.
Connect the sensor board to the DC-UPS by using control wires with a minimum wire size of 0.5mm
Instructions for replacement and disposal of batteries:
Batteries need to be replaced periodically. The time interval depends on the ambient temperature in which the battery is
used and on the number and depth of discharge cycles. In a typical application it is recommended to replace the batteries at
least every 2 years. Disconnect battery fuse before replacing the batteries.
Always dispose batteries through a recycling organization. Optionally, batteries can be returned to the supplier or the battery
manufacturer. Batteries must be completely discharged before recycling.
CAUTION: The unit contains wet cell batteries. Ventilation of the installation room in accordance with the rules of Canadian
Electrical Code, part 1 is required if used in Canada.
Rockwell Automation Support
For Technical Support, visit ROK.AUTO/SUPPORT.
The information in this document is believed to be accurate and reliable and may change without notice.
Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
www.rockwellautomation.com
Power, Control and Information Solution Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax. (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgien, Tel: (32) 2663.0600, Fax (32) 2663.0640
Asia Pacific: Rockwell Automation,Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887.4778, Fax (852) 2508.1846
Turkey: Rockwell Otomasyon Ticraet A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, Istanbul, Tel: (90) 216.5698400 (EEE Yönetmeliğine Uygundur)
Publication 1606-IN069A-EN-E - June 2020
(AWG 12). Do not use individual wires longer than 2m (7ft) to avoid voltage drops
2
Wiring Scheme
2
(AWG 20).
Mechanical Dimensions
Hole Pattern for Wall Mounting
Copyright © 2020 Rockwell Automation, Inc. All Rights Reserved..
All dimensions in mm
All dimension in mm
DIR 10005140965 (Version 01)