Ecoflam MAX P 15 AB LN CONFORT 100 Manual Del Usuario página 16

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 42
EN
Service
- Maintenance
Burner and boiler servicing must only
be carried out by qualified personell.
The system operator is advised to take
out a service contract to guarantee
regular servicing.
Attention
• Disconnect the electrical supply before
carrying out any maintenance or
cleaning work.
• The blast tube and firing head may be
hot.
5
Fan assembly
Observe the positioning diagram below
when replacing the motor and blower
wheel. The inside flange A of the blower
wheel must be fitted at the same level as
the equipment plate B. Insert a straight
edge between the wing of the blower wheel
and set A and B to the same height, tighten
the set screw on the blower wheel
(maintenance position 1).
16
www.ecoflam-burners.com
Checking the exhaust gas temperature
• Check the flue gas temperature at
regular intervals.
• Clean the boiler if the flue gas
temperature is more than 30°C above
the value measured at the time of
commissioning.
• To simplify the check, use a flue gas
temperature indicator.
Burner maintenance positions
• After removing the screws 5 turn the
burner and pull it out of the flange. It is
possible to fix the burner in three positions
1
for maintenance.
Position 1
Maintenance line air
(cleaning/substitution fan)
Position 2
Burner head maintenance.
Position 3
Maintenance components (filter and light
oil pump).
2
Maintenance on the burner
Maintenance position 1
• Clean fan and housing and check for
damage.
Maintenance position 2
• Check and clean the combustion head.
• Replace oil nozzle.
• Check ignition electrodes, readjust or
replace as necessary.
• Fit combustion head. Observe
adjustment dimensions.
• Fit burner.
• Start burner, check flue gas data, correct
burner settings if necessary.
Maintenance position 3
• Check oil supply components (tubes,
pumps, oil feed tube) and their
connections for leaks or signs of wear,
replace if necessary.
• Check electrical connections and
connection cables for damage, replace if
necessary.
• Check pump filter and clean if
necessary.
3
420011136900

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Max p 15 ab ln sp110Max p 15 ab ln sp235

Tabla de contenido