Central de incendios modular
Bus con red redundante
FPA-5000
001
FPA-5000
CAN1
CAN2
CAN1
CAN1
x100
x10
x1
001
Network Address: ________
Yes
On
1
CAN1 Termination
No
Off
Yes
On
2
CAN2 Termination
No
Off
Yes
On
CAN1 Ground Fault
3
Detection
No
Off
Yes
On
CAN2 Ground Fault
4
Detection
No
Off
Yes
CAN1_GND CAN2_GND
On
5
Connection
No
Off
Yes
On
PCTRL is
6
Redundant-PCTRL
No Off
Figura 7.17: Topología de bus con red redundante
Bosch Sicherheitssysteme GmbH
002
FMR-5000
CAN1
CAN2
CAN1
CAN2
CAN2
x100
x10
x1
002
Network Address: ________
Yes
On
1
CAN1 Termination
1
No
Off
Yes
On
2
CAN2 Termination
2
No
Off
Yes
On
3
NA
3
No
Off
Yes
On
4
NA
4
No
Off
CAN1_GND CAN2_GND
Yes
On
5
5
Connection
No
Off
Yes
On
6
NA
6
No Off
003
FPA-5000
L
max
CAN2
CAN1
CAN1
CAN2
x100
x10
x1
x100
003
Network Address: ________
Network Address: ________
Yes
On
CAN1 Termination
1
No
Off
Yes
On
2
CAN2 Termination
No
Off
Yes
On
CAN1 Ground Fault
3
Detection
No
Off
Yes
On
CAN2 Ground Fault
4
Detection
No
Off
Yes
CAN1_GND CAN2_GND
On
5
Connection
No
Off
Yes
On
PCTRL is
6
Redundant-PCTRL
No Off
Networking Guide
004
005
FMR-5000
FPA-5000
CAN1
CAN2
CAN1
CAN2
x10
x1
x100
004
Network Address: ________
Yes
On
1
CAN1 Termination
CAN1 Termination
No
Off
Yes
On
2
CAN2 Termination
CAN2 Termination
No
Off
Yes
On
CAN1 Ground Fault
3
NA
No
Off
Yes
On
CAN2 Ground Fault
4
NA
No
Off
Yes
CAN1_GND CAN2_GND
On
CAN1_GND CAN2_GND
5
Connection
No
Off
Yes
On
PCTRL is
NA
6
Redundant-PCTRL
No Off
2017.04 | 5.5 | F.01U.247.450
Instalación | es
59
CAN2
x10
x1
005
Yes
On
No
Off
Yes
On
No
Off
Yes
On
Detection
No
Off
Yes
On
Detection
No
Off
Yes
On
Connection
No
Off
Yes
On
No Off