Carrier 07KD Instrucciones De Instalación, Funcionamiento Y Mantenimiento página 20

Tabla de contenido

Publicidad

Suction line / Linea di aspirazione / Conduite d'aspiration
Sauggasleitung / Línea de aspiración
Pressure loss/10 m of equivalent length • Perdita di pressione/10 m di lunghezza equivalente • Perte de charge/10 m de
longueur équivalente • Druckverlust/10 m gleichwertige Länge • Perdida de presión/10 m de longitud equivalente
Refrigerant line connection
(Flare connnections)
From the drawing and for the unit selected
for each diameter we can obtain the
pressure drop corresponding to a line of 10
m, of equivalent length. For other
equivalent lengths, the pressure drop is
obtained by direct proportion.The total
pressure drop for the line (the sum
corresponding to the horizontal and vertical
stretches) must not be bigger than 3 psi or
20 kPa.
20
Collegamento linea refrigerante
(attacchi a cartella)
Se si osserva il grafico in cui appare l'unità
scelta per ogni diametro, è possibile
ottenere la caduta di pressione corrispon-
dente alla linea, con una lunghezza di 10m
equivalenti. Per le altre lunghezze equiva-
lenti, la caduta di pressione è direttamente
proporzionale. La caduta di pressione totale
per linea (vengono sommati i tratti orizzon-
tale e verticale) non deve essere superiore
a 3 psi o a 20 kPa.
07KD 010 +
07KD 015/018 +
07KD 024 +
07KD 028 +
07KD 036 +
07KD 048 +
07KD 060 +
Indoor unit
Unità interna
Unité intérieure
Innengeräte
Unidad interior

Publicidad

Tabla de contenido
loading

Tabla de contenido